9 Setting Up Slave Terminals
9 - 8
NX-series EtherNet/IP Coupler Unit User’s Manual (W536)
Setting Settable Description
Data
range
Default
Device name This is the name of the EtherNet/IP Coupler Unit.
Use the EtherNet/IP Configuration Edit Tab Page to
change this setting.
--- E *** (* is a serial
number from
001).
The default value
is automatically
generated based
on the node
address.
Model name This is the model of the EtherNet/IP Coupler Unit. --- The model num-
ber of the Ether-
Net/IP Coupler
Unit is shown.
Product name This is the product name. --- EtherNet/IP Cou-
pler
Unit version This is the Unit version of the EtherNet/IP Coupler Unit. --- ---
NX Unit Number This number represents the logical position of the Eth-
erNet/IP Coupler Unit.
--- 0
NX Unit Mounting
Setting
This setting enables or disables the mounting of an NX
Unit. You cannot directly edit these settings in the Eth-
erNet/IP Coupler Unit.
--- ---
Serial Number This is the serial number of the EtherNet/IP Coupler
Unit. You can get the serial number to set the serial
number of the actual EtherNet/IP Coupler Unit.
--- ---
Supply
Power/Available
Power [W]
The power that is currently drawn by the NX Units and
the maximum available power supply capacity are
given.
--- -/10.00
Unit width [mm] This is the width of the EtherNet/IP Coupler Unit. --- 46
I/O allocation set-
tings
Yes These are the I/O allocation settings for the EtherNet/IP
Coupler Unit. Click the Edit I/O Allocation Settings
button to edit these settings.
--- Refer to 9-2-3 I/O
Allocation Infor-
mation on page
9-12.
Unit operation set-
tings
Yes These are the Unit operation settings for the Ether-
Net/IP Coupler Unit. Click the Edit Unit Operation Set-
tings button to edit these settings.
--- Refer to 9-2-4
Unit Operation
Settings on page
9-22.
Number of mounted
Units
This is the number of mounted NX Units. --- ---
NX Unit Connection
Time (s)
Yes This is the wait time for the NX Units to connect to the
Slave Terminal.
3 to 200 s 3 s
Serial Number
Check Method
Yes Set this setting to Setting = Actual device to compare
the serial numbers of the NX Units at these times: when
the power is turned ON and after the EtherNet/IP Cou-
pler Unit is restarted. The serial numbers of the NX
Units saved in the Unit configuration information are
compared with the actual serial numbers of the NX
Units.
*1
If differences are found, a Unit Configuration Verifica-
tion Error will occur.
*1. If this setting is set to Setting = Actual device and you replace an NX Unit in the Slave Terminal, a Unit Config-
uration Verification Error will occur. A Unit Configuration Verification Error will also occur if you swap the mount-
ing position of two Units of the same model. If it becomes necessary to replace an NX Unit, or swap the
mounting positions of two Units of the same model while this setting is set to Setting = Actual device, you must
correct the Unit configuration information and download it to the EtherNet/IP Coupler Unit. Set this parameter
to Setting = Actual device if strict management of the equipment configuration is required.
No check.
Setting =
Actual
device
No check.