7-71
7 Tag Data Link Functions
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
7-2 Setting Tag Data Links
7
7-2-13 Clearing the Device Parameters
Yes Button:
The following dialog box is displayed.
Select the Initialize tag data link configuration, and then emulate cycling power Option and then click
the OK Button.
Precautions for Correct UsePrecautions for Correct Use
The Controller is not restarted. Only the built-in EtherNet/IP port is reset.
No Button:
The tag data link settings will not be cleared and the built-in EtherNet/IP port will not be reset.
Additional Information
You can also execute the Reset service of the Identity object for the CPU Unit to clear the tag
data link settings. The procedures to execute the service from the Network Configurator is given
below.
(1) Connect the Network Configurator to the network.
(2) Select Tool - Setup Parameters on the main window.
Then the dialog box for the general parameter settings are displayed.
(3) Specify the target device and message to send.
• Target Node Address: Enter the IP address of the target device.
• Service: Select Reset.
• Class: Enter 01.
• Instance: Enter 01.
• Attribute: Enter 00.
• Data: Enter 02.*
(4) Click the Send Button.
* For a CPU Unit version 1.09 or earlier, specify 01.

Table of Contents

Other manuals for Omron Sysmac NJ-series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron Sysmac NJ-series and is the answer not in the manual?

Omron Sysmac NJ-series Specifications

General IconGeneral
BrandOmron
ModelSysmac NJ-series
CategoryComputer Hardware
LanguageEnglish

Related product manuals