14-7
14 Communications Performance and Communications Load
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
14-2 Adjusting the Communications Load
14
14-2-1 Checking Bandwidth Usage for Tag Data Links
The Network Configurator can display the bandwidth actually used for tag data links at each built-in Eth-
erNet/IP port, based on the connections set in the network configuration. The device bandwidth used by
tag data links can be checked by clicking the Detail Button in the Usage of Device Bandwidth Area at
the bottom of the Network Configuration Window.
14-2-1 Checking Bandwidth Usage for Tag Data Links
Item Description
# The IP address of the device.
Comment A description of the device. The comment is displayed below the device icon.
The model number of the device is displayed by default.
Usage of Capacity (without Multi-
cast Filter)
The percentage of the allowable communications bandwidth used for tag
data links for the device is displayed. Bandwidth used ÷ Allowable tag data
link bandwidth
The values outside parentheses are for when multicast filtering is used.
The values inside parentheses are for when multicast filtering is not used.
Mbit/s (without Multicast Filter) The bandwidth used for communications by the device of the network band-
width is shown.
The values outside parentheses are for when multicast filtering is used.
The values inside parentheses are for when multicast filtering is not used.
Usage of IP Multicast Addresses The number of multicast IP addresses actually used for communications by
the device is shown.
Total usage of IP multicast
addresses
The number of multicast IP addresses used in the entire network is shown.
This value is used to estimate the number of multicast filters for switching.
Network Total of Max. Mbit/s The total network bandwidth used for tag data link communications in the
entire network is shown. Tag data links will not operate normally if the net-
work bandwidth that can be set is exceeded.

Table of Contents

Other manuals for Omron Sysmac NJ-series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron Sysmac NJ-series and is the answer not in the manual?

Omron Sysmac NJ-series Specifications

General IconGeneral
BrandOmron
ModelSysmac NJ-series
CategoryComputer Hardware
LanguageEnglish

Related product manuals