1 Introduction
1-22
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
1-5 EtherNet/IP Communications
Procedures
Basic Operation
Using Tag Data Links
1-5-1 Outline
1
Wire the Ethernet network with twisted-pair cable.
Section 2 Installing Ethernet
Networks
↓
2
Set the built-in EtherNet/IP port IP address with the Sysmac Studio.
Section 4 Determining IP
Addresses
1. Use the Sysmac Studio to create a new project.
2. Set the local IP address in one of the following ways:
• Defaults:
NX701 CPU Unit
Built-in EtherNet/IP port 1 : 192.168.250.1
(subnet mask = 255.255.255.0)
Built-in EtherNet/IP port 2 : 192.168.251.1
(subnet mask = 255.255.255.0)
NX1P2 CPU Unit
Built-in EtherNet/IP port 1
: 192.168.250.1
(subnet mask = 255.255.255.0)
NJ-series CPU Unit
Built-in EtherNet/IP port
• Set any IP address.
• Obtain from BOOTP server.
↓
3
Perform a communications test with a PING command from a com-
puter.
Section 6 Testing Communi-
cations
↓
4
Use the Sysmac Studio to set the initial settings of the EtherNet/IP
Function Module.
Section 5 Sysmac Studio
Settings for the Built-in Eth-
erNet/IP Port
Set the TCP/IP settings and Ethernet settings as required.
1
Import the variable settings for the tags that were created on the
Sysmac Studio to the Network Configurator.
7-2-4 Creating Tags and Tag
Sets
↓
2
Use the Network Configurator to create the tag data link table.
Section 7 Tag Data Link
Functions
• Create the network configuration.
• Set the tags, tag sets, and connections.
↓
3
Connect the Network Configurator online.
↓