31
ENFORCER V11 PROGRAMMING GUIDE
To view additional details, press the c key. If no other information is available, the display will move to the next
log entry. Pressing a will return to the main screen for that entry.
Please note: For all ‘Fault Codes’, see Appendix E - Fault Finding” on page 57.
ENGINEER TESTS
ENGINEER TESTS?
Sound to Play?
Walk Test?
Soak Control?
Test Siren?
Do Battery Load Test?
Test Outputs?
Test Communications?
Fetch Time?
Poll Test Server?
The test functions allow the engineer to test zones, outputs, batteries and the siren.
Sound to play
This function previews all of the dierent tones the system makes. They have a choice of:
Chime
Chime Follow
Exit
Exit Fault
Entry
Tech Fault
Tamper
Alarm
PA
Fire
Walk test
The walk test feature is used to test all the zones programmed on the system. It is recommended that after
programming any zones, the Engineer menu is exited to save all data, after this point a walk test should be
performed. The zones that haven’t been activated will be shown on the display. Once all the zones have been
walk tested, Walk Test Completed’ will be displayed.
Hint: When walk-testing a double-knock detector, it must be triggered twice within the dened period. When testing dual-trip detectors, the rst
detector must be triggered and then the second detector; next, trigger the second detector and trigger the rst detector.
Please note: To walk test a specic zone, press h instead of selecting areas. Then specic zones can be
entered with the numerical keys, pressing after each zone. Then press h to walk test them.
Soak control
Any zone may be placed on ‘soak test’ which monitors the detector without giving an alarm activation. If the
chosen zone triggers whilst the system is set, it will indicate the activation and enter the details in the event log.
The number of days the zone is in soak control before the zone becomes active can be programmed.
Please note: The ‘Initial Soak time should be set to equal or greater than the ‘Soak Days Left.

Table of Contents

Other manuals for Pyronix ENFORCER V11

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pyronix ENFORCER V11 and is the answer not in the manual?

Pyronix ENFORCER V11 Specifications

General IconGeneral
BrandPyronix
ModelENFORCER V11
CategorySecurity System
LanguageEnglish

Related product manuals