Rockwell Automation Publication 7000-UM202H-EN-P - November 2023 201
Appendix D Insulation Resistance Test
Grounding Network
b. Reconnect the ground connection on the GN capacitor. The bolt
connection should torque down to 3.4 N•m (30 lb•in). Exceeding the
torque rating of this connection may result in damage to the capacitor.
Failure to reconnect the GN ground may result in impressing the
neutral voltage offset on the motor cables and stator, which may result
in equipment damage. For drives that did not originally have the GN
connected (or even installed), this is not a concern.
Transient Suppression Network
c. Re-install the fuses on the TSN.