LMV Series Technical Instructions
Document No. LV3-1000
SCC Inc. Page 17 Section 5
Name and Timing of Speed Band
Neutral Band
No Time Limit
Near Zone Band
8 to 16 sec
Zone 3 to 7
seconds
Limit
1 second
High Limit of Speed Band +0.5% to 3.5% +2.0% to 5.5% Near to +10%
greater
Parameter to Adjust Width of Band
Parameter to Adjust Band Timing
RPM Tolerance for Standardized Speed
of 3544 RPM
Neutral Band = 2%, Near Zone = 4%
+/- 71 +/- 142 +/- 354
More than
+/- 354
Time VSD
Standardized
speed line
Max Min Max Min Max Min
RAMP UP
Figure 5-5: Blower Speed Monitoring Bands
1200
1450
1700
1950
2200
2450
2700
2950
3200
3450
3700
3950
4200
0 10 20 30 40
Blower Speed (RPM)
Time (sec)
Standardized Baseline
Neutral Max
Neutral Min
Near Zone Max
Near Zone Min
High Risk Limit
High Risk Limit
Blower Speed Monitoring Bands