LMV Series Technical Instructions
Document No. LV3-1000
SCC Inc. Page 13 Appendix A
Low Fire Hold with an RWF55 (continued)
Operation
1. When the boiler temperature falls below the low fire hold temperature threshold
(AL - 1/2 HYSt), contact K6 opens and prevents the LMV3 from increasing the firing rate.
This is the case for either analog or 3-position output from the RWF55.
2. Once the boiler warms up above the low fire hold threshold (AL + 1/2 HYSt), contact K6
closes and the burner modulates according to the PID settings of the RWF55.
Example
Low fire hold threshold settings:
AL = 180
HYSt = 10
Figure 7: Behavior of Contact K6 when Using an RWF55 for Low Fire Hold