Special functions of the CPU 410
9.8 Resetting the CPU 410 to delivery condition (reset to factory setting)
CPU 410 Process Automation/CPU 410 SMART
142 System Manual, 05/2017, A5E31622160-AC
9.8
Resetting the CPU 410 to delivery condition (reset to factory setting)
CPU factory settings
A general memory reset is performed when you reset the CPU to its factory settings and the
properties of the CPU are set to the following values:
Table 9- 2 CPU properties in the factory settings
Properties
Value
Contents of the diagnostics buffer
Empty
IP parameters None
SNMP parameters
Default values
Operating hours counter
0 without battery backup
Contents of the load memory
Empty
Procedure
Proceed as follows to reset a CPU to its factory settings:
1. Switch off the line voltage.
2. Switch on the line voltage while pressing and holding down the Reset button.
3. Wait until LED lamp image 1 from the subsequent overview is displayed. In this lamp
pattern, INTF flashes at 0.5 Hz. EXTF, BUSxF, MAINT, IFMxF, RUN, and STOP remain
unlit.
4. Wait until LED lamp image 2 from the subsequent overview is displayed. In this LED
pattern, INTF is lit. EXTF, BUSxF, MAINT, IFMxF, RUN, and STOP remain unlit.
5. The CPU performs a memory reset and the STOP LED flashes at 2 Hz.
The CPU is now reset to its factory settings. It starts up and switches to STOP operating
state or links up. The event "Reset to factory setting" is entered in the diagnostics buffer.
LED patterns during CPU reset
While you are resetting the CPU to its factory settings, the LEDs light up consecutively in the
following LED patterns:
Table 9- 3 LED patterns
LED
LED pattern 1
LED pattern 2
INTF
Flashes at 0.5 Hz Lit
EXTF
Dark
Dark
BUSxF
Dark
Dark
MAINT
Dark
Dark
IFMxF
Dark
Dark

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC CPU 410 and is the answer not in the manual?

Siemens SIMATIC CPU 410 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC CPU 410
CategoryControl Unit
LanguageEnglish

Related product manuals