Plant changes in RUN - CiR
11.10 Notes on Reconfiguration in RUN Mode Depending on the I/O
CPU 410 Process Automation/CPU 410 SMART
System Manual, 05/2017, A5E31622160-AC
193
Adding a DP/PA Link with PA Master System
Adding a DP/PA link and its corresponding PA master system corresponds with the insertion
of a new DP slave in an existing DP master system.
11.10.3
Modules in ET 200M Modular Slaves
Principle
When you are planning systems during operation via CiR, you must observe the following
already at the planning stages:
Install the ET 200M station with an active backplane bus.
Always try to equip the station with the maximum number of bus modules, as you can not
insert or remove a bus module during runtime.