EasyManuals Logo
Home>Siemens>Control Unit>SIMATIC CPU 410

Siemens SIMATIC CPU 410 User Manual

Siemens SIMATIC CPU 410
434 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #227 background imageLoading...
Page #227 background image
Replacement of failed components during redundant operation
13.1 Replacement of central components
CPU 410 Process Automation/CPU 410 SMART
System Manual, 05/2017, A5E31622160-AC
227
To replace signal and function modules of an S7-400, perform the following steps:
Step
What to do?
How does the system react?
1 Disconnect the module from its peripheral
power supply, if necessary.
2 Disconnect the front connector and wiring.
• If the affected module can generate
diagnostic interrupts and if diagnostic in-
terrupts are enabled as per configura-
tion, a diagnostic interrupt is generated.
• Call OB 122 if you are accessing the
module by direct access
• Call OB 85 if you are accessing the
module using the process image
3 Remove the failed module (in RUN mode).
• Both CPUs generate a remove/insert
interrupt and enter the event in the di-
agnostic buffer and the system status
list.
4 Insert the new module.
• Both CPUs generate a remove/insert
interrupt and enter the event in the di-
agnostic buffer and the system status
list.
• Parameters are assigned automatically
to the module by the CPU concerned
and the module is addressed again.
5 Plug the front connector into the new mod-
ule.
• If the affected module can generate
diagnostic interrupts and if diagnostic in-
terrupts are enabled as per configura-
tion, a diagnostic interrupt is generated.
13.1.4
Replacement of a communication module
This section describes the failure and replacement of communication modules for
PROFIBUS and Industrial Ethernet.
The failure and replacement of communication modules for PROFIBUS DP is detailed in
Replacement of a PROFIBUS DP master (Page 234).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC CPU 410 and is the answer not in the manual?

Siemens SIMATIC CPU 410 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC CPU 410
CategoryControl Unit
LanguageEnglish

Related product manuals