Supplementary information
18.16 CPU 410 cycle and reaction times
CPU 410 Process Automation/CPU 410 SMART
376 System Manual, 05/2017, A5E31622160-AC
18.16.9
Reproducibility of delay and watchdog interrupts
Definition of "reproducibility"
Time-delay interrupt:
The period that expires between the call of the first operation in the interrupt OB and the
programmed time of interrupt.
Cyclic interrupt:
The fluctuation range of the interval between two successive calls, measured between the
respective initial operations of the interrupt OB.
Reproducibility
The following table contains the reproducibility of time-delay and cyclic interrupts of the
CPUs.
Table 18- 20 Reproducibility of time-delay and cyclic interrupts of the CPUs
Module
Reproducibility
Time-delay interrupt
Cyclic interrupt
CPU 410-5H stand-alone mode
± 120 µs
± 160 µs
CPU 410-5H redundant
± 200 µs
± 180 µs
These times only apply if the interrupt can actually be executed at this time and if it is not
delayed, for example, by higher-priority interrupts or queued interrupts of equal priority.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC CPU 410 and is the answer not in the manual?

Siemens SIMATIC CPU 410 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC CPU 410
CategoryControl Unit
LanguageEnglish

Related product manuals