Characteristic values of redundant automation systems
A.2 Comparison of MTBF for selected configurations
CPU 410 Process Automation/CPU 410 SMART
System Manual, 05/2017, A5E31622160-AC
383
The availability of a system is expressed as a percentage. It is defined by the mean time
between failure (MTBF) and the mean time to repair MTTR (MDT). The availability of a two-
channel (1-out-of-2) fault-tolerant system can be calculated using the following formula:
Figure A-4 Availability
A.2
Comparison of MTBF for selected configurations
The following sections compare systems with a centralized and distributed I/Os.
The following framework conditions are set for the calculation.
MDT (Mean Down Time) 4 hours
Ambient temperature 40 degrees
Buffer voltage is safeguarded
A.2.1
System configurations with redundant CPU 410
The following system with one CPU (e.g., CPU 410-5H PN/DP) in stand-alone operation
serves as the basis for calculating a reference factor that defines the multiple of the system
MTBF of other systems with centralized I/O compared with the base line.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC CPU 410 and is the answer not in the manual?

Siemens SIMATIC CPU 410 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC CPU 410
CategoryControl Unit
LanguageEnglish

Related product manuals