Supplementary information
18.17 Runtimes of the FCs and FBs for redundant I/Os
CPU 410 Process Automation/CPU 410 SMART
System Manual, 05/2017, A5E31622160-AC
377
18.17
Runtimes of the FCs and FBs for redundant I/Os
Table 18- 21 Runtimes of the blocks for redundant I/Os
Block
Runtime in stand-alone/single mode
Runtime in redundant mode
FC 450 RED_INIT
Specifications are based
on the startup
2 ms + 300 µs / configured module pairs
The specification for a module pair is a mean
value. The runtime may be < 300 µs for a few
modules. For a large number of redundant
modules the value may be > 300 µs.
-
FC 451 RED_DEPA 160 µs 360 µs
FB 450 RED_IN
Called from the corre-
sponding sequence level.
750 μs + 60 μs / module pair of the current
TPA
The specification for a module pair is a mean
value.
The runtime may be additionally increased if
discrepancies occur resulting in passivation
and logging to the diagnostic buffer.
The runtime may also be increased by a
depassivation carried out at the individual
sequence levels of FB RED_IN. Depending
on the number of modules in the sequence
level, the depassivation may increase the
runtime of the FB RED_IN by 0.4 ... 8 ms.
An 8 ms increase can be expected in redun-
dant operation of modules totaling more than
370 pairs of modules at a sequence level.
1000 μs + 70 μs / module pair of the current
TPA
The specification for a module pair is a mean
value.
The runtime may be additionally increased if
discrepancies occur resulting in passivation
and logging to the diagnostic buffer.
The runtime may also be increased by a
depassivation carried out at the individual
sequence levels of FB RED_IN. Depending
on the number of modules in the sequence
level, the depassivation may increase the
runtime of the FB RED_IN by 0.4 ... 8 ms.
An 8 ms increase can be expected in redun-
dant operation of modules totaling more than
370 pairs of modules at a sequence level.
FB 451 RED_OUT
Called from the corre-
sponding sequence level.
650 μs + 2 μs / module pair of the current
TPA
The specification for a module pair is a mean
value. The runtime may be < 2 µs for a few
modules. For a large number of redundant
modules the value may be > 2 µs.
860 μs + 2 μs / module pair of the current
TPA
The specification for a module pair is a mean
value. The runtime may be < 2 µs for a few
modules. For a large number of redundant
modules the value may be > 2 µs.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC CPU 410 and is the answer not in the manual?

Siemens SIMATIC CPU 410 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC CPU 410
CategoryControl Unit
LanguageEnglish

Related product manuals