Replacement of failed components during redundant operation
13.1 Replacement of central components
CPU 410 Process Automation/CPU 410 SMART
System Manual, 05/2017, A5E31622160-AC
229
Starting situation
Failure
How does the system react?
Failure of a fiber-optic cable or synchronization
module:
The S7-400H is in the redundant system state
and a fiber-optic cable or synchronization module
fails.
See also chapter Synchronization modules for
the CPU 410. (Page 239).
• Master CPU reports the event in the diagnos-
tic buffer and through OB 72 or OB 82.
• The standby CPU switches to ERROR-
SEARCH operating state for a few minutes. If
the error is eliminated during this time, the
standby CPU switches to redundant system
mode, otherwise it switches to STOP.
• One of the two LEDs Link1 OK or Link2 OK is
lit
One of the two LEDs IFM1F or IFM2F is lit
Procedure
Follow the steps below to replace a fiber-optic cable:
Step
What to do?
How does the system react?
1
Look for the cause of the error along the path
for which the IFMxF LEDs are lit on both
CPUs:
IFM1F: Upper sync modules in CPU rack 0
or rack 1 or corresponding synchronization
cable.
IFM2F: Lower sync modules in CPU rack 0
or rack 1 or corresponding synchronization
cable.
First, check the fiber-optic cable.
-
2
If the fiber-optic cable is defective, replace it.
The IFMxF LEDs on both CPUs go out.
Follow the steps below to replace a synchronization module:
Step
What to do?
How does the system react?
1 Replace the synchronization module on the
CPU on which the LED Linkx-OK is still lit.
-
2 Plug in the fiber-optic cable connections of
the synchronization modules.
• The LEDs IFMxF go out.
If the LED should not go out, you must
replace the synchronization module on
the other CPU.
• Both CPUs report the event in the diag-
nostic buffer
3 Start the standby CPU The system status now changes to Redun-
dant mode.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC CPU 410 and is the answer not in the manual?

Siemens SIMATIC CPU 410 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC CPU 410
CategoryControl Unit
LanguageEnglish

Related product manuals