Technical data
16.2 Technical specifications of CPU 410E (6ES7410-5HM08-0AB0)
CPU 410 Process Automation/CPU 410 SMART
270 System Manual, 05/2017, A5E31622160-AC
– Open IE communication
Yes
– Shared device
No; however, usable as part of S7
– Prioritized startup
No
– Number of connectable IO Devices,
max.
250
– Number of connectable IO Devices for
RT, max.
250
– of which in line, max.
250
– Activation/deactivation of IO Devices
Yes; Single mode only
– IO Devices changing during operation
(partner ports), supported
No
– Device replacement without swap me-
dium
Yes
– Send cycles
250 µs, 500 µs, 1 ms, 2 ms, 4 ms
– Updating time
250 µs to 512 ms, minimum value depends on
the number of configured user data and the con-
figured single or redundant mode
– Inputs, max.
1 536 byte; Up to 1 500 IOs (channels)
– Outputs, max.
1 536 byte; Up to 1 500 IOs (channels)
– User data consistency, max.
1 024 byte
• Number of connections, max.
118
• Local port numbers used at the system end
0, 20, 21, 25, 102, 135, 161, 34962, 34963,
34964, 65532, 65533, 65534, 65535
• Keep-alive function, supported
Yes
Pluggable synchronization submodule (FO)
Plug-in interface modules Synchronization module 6ES7960-1AA06-0XA0,
6ES7960-1AB06-0XA0 or 6ES7960-1AA08-0XA0
Pluggable synchronization submodule (FO)
Plug-in interface modules Synchronization module 6ES7960-1AA06-0XA0,
6ES7960-1AB06-0XA0 or 6ES7960-1AA08-0XA0
Supports protocol for PROFINET IO
• TCP/IP
Yes