Technical data
16.2 Technical specifications of CPU 410E (6ES7410-5HM08-0AB0)
CPU 410 Process Automation/CPU 410 SMART
272 System Manual, 05/2017, A5E31622160-AC
Article number
6ES7410-5HM08-0AB0
• Number of instances for alarm 8 and S7
communication blocks, max.
10 000
• preset, max.
10 000
Process control messages
Yes
Test commissioning functions
Status block Yes
Single step
Yes
Number of breakpoints
4
Status/control
• Status/control variable
Yes
• Variables
Inputs/outputs, memory bits, DBs, distributed
I/Os, timers, counters
• Number of variables, max.
70
Diagnostic buffer
• present
Yes
• Number of entries, max.
3 200
Service data
• can be read out
Yes
Standards, approvals, certificates
CE mark
Yes
CSA approval
Yes
UL approval
Yes
cULus
Yes
FM approval
Yes
RCM (formerly C-TICK)
Yes
KC approval
Yes
EAC (formerly Gost-R)
Yes
Use in hazardous areas
• ATEX
ATEX II 3G Ex nA IIC T4 Gc
Ambient conditions
Ambient temperature during operation
• min.
0 °C
• max.
70 °C
Configuration
Know-how protection
• User program protection/password protec-
tion
Yes
• Block encryption
Yes; With S7 block Privacy

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC CPU 410 and is the answer not in the manual?

Siemens SIMATIC CPU 410 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC CPU 410
CategoryControl Unit
LanguageEnglish

Related product manuals