Supplementary information
18.2 Supplementary information on diagnostics of the CPU 410 as PROFIBUS DP master
CPU 410 Process Automation/CPU 410 SMART
300 System Manual, 05/2017, A5E31622160-AC
Event detection
The following table shows how the CPU 41xH in DP master mode detects operating state
changes on a DP slave or interruptions of the data transfer.
Table 18- 2 Event detection of the CPU 41xH as a DP master
Event
What happens in the DP master?
Bus interruption due to short-circuit or
disconnection of the connector
• OB 86 is called with the message
Station failure
as an incoming event; diag-
nostics address of the DP slave assigned to the DP master
• With I/O access: Call of OB 122, I/O area access error
DP slave: RUN → STOP
• OB 82 is called with the message
Module error
as incoming event; diagnostic
address of the DP slave assigned to the DP master; variable
OB82_MDL_STOP=1
DP slave: STOP → RUN
• OB 82 is called with the message
Module OK
as incoming event; diagnostic
address of the DP slave assigned to the DP master; variable
OB82_MDL_STOP=0
Evaluation in the user program
The table below shows you how to evaluate RUN-STOP changes of the DP slave on the DP
master. Also refer to the previous table.
On the DP master
On the DP slave (CPU 41x)
• Example of diagnostic addresses:
Master diagnostics address=1023
Slave diagnostics address in master
system=1022
• Example of diagnostic addresses:
Slave diagnostics address=422
Master diagnostics address=irrelevant
The CPU calls OB 82 with the following information, for example:
• OB 82_MDL_ADDR:=1022
• OB82_EV_CLASS:=B#16#39
As incoming event
• OB82_MDL_DEFECT:=module error
The CPU diagnostic buffer also contains this information.
Your user program should also be set up to read the diagnostic
data of the DP slave using SFC 13 "DPNRM_DG".
Use SFB 54 in the DPV1 environment. It outputs the full interrupt
information.
CPU: RUN → STOP
CPU generates a DP slave diagnostics frame.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC CPU 410 and is the answer not in the manual?

Siemens SIMATIC CPU 410 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC CPU 410
CategoryControl Unit
LanguageEnglish

Related product manuals