I/O configuration variants
6.6 Versions of I/O connection to the PROFINET IO interface
CPU 410 Process Automation/CPU 410 SMART
System Manual, 05/2017, A5E31622160-AC
77
This terminal block connects the respective process signals of the two IO modules to a
common process terminal.
There is less wiring work compared to connecting separate I/O modules, because the
interconnection of the process signals is integrated in the system.
The redundant signal processing of the sensors and actuators on the module level
increases the availability of the system.
In redundant operation, the switching characteristics of the output modules that can
control the actuator in parallel are improved.
Application planning
Observe the following rules for configuring redundant I/O modules:
Hardware rule
The I/O modules must be approved for redundant operation. You can find this information
in the manual for the respective module.
Redundantly deployed I/O modules must be identical, i.e. they must have the same article
number, the same hardware version and the same firmware version.
Mounting rule
I/O modules of the same type are plugged in pairs next to each other in the same IO device.
Both slots are located on the same support module.
Both slots are located on the same terminal block (
TB45R
).
Note
Specific wiring
Always read the documentation of the I/O module used.
Configuring
Configure redundancy for the I/O module.
The settings you make for an I/O module always apply to the module pair.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC CPU 410 and is the answer not in the manual?

Siemens SIMATIC CPU 410 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC CPU 410
CategoryControl Unit
LanguageEnglish

Related product manuals