7-12
Equipment
Manual OP7, OP17
Release 04/99
7.4 Deleting
Messages
All
message events for event and alarm messages are automatically stored in
the event message buf
fer or alarm message buffer respectively
. Each of these
buf
fers has space for up to 256 events. T
o prevent a buf
fer overflow
, event
and alarm messages must be deleted from their buf
fers.
Message events from the event message buf
fer or alarm message buf
fer are
deleted
automatically when buf
fer overflow occurs
by means of the appropriate standard screen.
System messages are deleted automatically only when the buf
fer overflows.
7.4.1 Deleting alarm message and event message buffers upon buffer
overflow
When
the specified remaining buffer capacity for the alarm and event mes
-
sage buf
fers is reached, an overflow warning is output by default. Output of
this overflow warning can be activated and deactivated online via the corre
-
sponding standard screen:
Alarms
Overflow
Events
Overflow
If the alarm or event message buf
fer has insuf
ficient space to accept any
more message events, message events are automatically deleted until the spe
-
cified remaining buf
fer capacity is reached. Deletion is carried out in the fol
-
lowing order:
The oldest departed messages.
For departed event messages, the message events ’arrival’ and ’departure’
are deleted. For departed alarm messages, the message events ’arrival’,
departure’ and ’acknowledged’ are deleted.
Queued messages.
If there is still insuf
ficient space for new events, the oldest queued mes
-
sages are deleted in the case of event messages.
In the case of alarm messages, deletion is carried out in the following or
-
der:
Acknowledged alarm messages yet to depart
Unacknowledged alarm messages that have already departed
Unacknowledged alarm messages yet to depart.
If “Printout Overflow” has been configured and a printer is connected to the
OP and switched on, a forced printout of all deleted messages is initiated.
Purpose
Overflow
warning
Deleting upon
buffer overflow
Automatic printout

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens simatic hmi op7 and is the answer not in the manual?

Siemens simatic hmi op7 Specifications

General IconGeneral
BrandSiemens
Modelsimatic hmi op7
CategoryControl Panel
LanguageEnglish

Related product manuals