Additional system components
7.3 Sensor Module Cabinet-Mounted SMC30
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
219
7.3.8
Protective conductor connection and shield support
Shield supports are only required if the system is connected to X521/X531.
â‘ 
Protective conductor connection with M4 screw / 1.8 Nm
â‘¡
Shield connection terminal, Weidmüller company, type: KLBUE CO1,
Article number: 1753311001
Figure 7-13 Shield support and PE conductor connection
The bending radii of the cables must be observed (see MOTION-CONNECT description).
Note
Only use screws with a permissible mounting depth of 4
- 6 mm.
NOTICE
Damage or faulty operation due to incorrect shielding and impermissible cable lengths
If the correct shielding procedures and the permissible cable lengths are not observed, the
machine can be damaged or may malfunction.
• Only use shielded cables.
• Do not exceed the cable lengths stated in the technical data.

Table of Contents

Other manuals for Siemens SINAMICS DCM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS DCM and is the answer not in the manual?

Siemens SINAMICS DCM Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS DCM
CategoryMedia Converter
LanguageEnglish

Related product manuals