SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
709
Functional safety
13
13.1
Functional safety: Deactivated Activated
STO circuit deactivated
Jumper in terminal X200/1:2 (STO to P24): STO circuit is deactivated.
Here, the STO input is deactivated and the STO is therefore deselected. Converter operation
is possible independent of the signal states at the STO input.
The converter is supplied in this state. The terminals 105 and 106 are jumpered in the
delivery state (no emergency stop).
Applications where STO is not used.
STO circuit activated
Jumper in terminal X200 must be removed: STO circuit is activated.
Safety relay can be connected.
13.2
General technical specifications of the DCM (6RA80)
Table 13- 1 SINAMICS DCM
Functional safety
MTTF
D
according to ISO 13849-1
500 years
Diagnostics coverage (DC) according to ISO 13849-1/IEC 61508
99%
Maximum operating altitude above MSL 4000 m
1)
T1 value for proof test interval or service duration according to
ISO 13849-1/IEC 61508
20 years
Response time when activating STO
Maximum 250 ms
1)
For installation altitude > 2000 m, select a suitable safety relay and coupling relay (contactor
relay).

Table of Contents

Other manuals for Siemens SINAMICS DCM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS DCM and is the answer not in the manual?

Siemens SINAMICS DCM Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS DCM
CategoryMedia Converter
LanguageEnglish

Related product manuals