Descriptions of functions
10.6 Communication via SINAMICS Link
SINAMICS DCM DC Converter
518 Operating Instructions, 12/2018, A5E34763375A
Table 10- 44 Compile send data of Control Unit 1 (DO1)
p2051[x]
Index
p2061[x]
Index
Contents
From
parameter
Slots in the send buffer
p8871[x]
x
Telegram
word
-
-
-
-
0...11
2)
0
0
-
Control word, faults/alarms
r2138
12
13
- 1 Missing enables part 1 r0046 13 14
-
Missing enables part 2
14
15
15 - 0 0 15 0
...
-
...
-
...
...
31
-
0
0
31
0
2)
0...11 here remain free, as they are already assigned by DO2 and DO3.
Send slots PZD 16 to 31 are not required for this telegram and are therefore filled with a
zero.
1. For double words (e.g. 1 + 2), assign two consecutive send slots, e.g.
p2061[1] => p8871[1] = PZD 2 and p8871[2] = PZD 3.
2. Enter the following PZD into the next parameter slots of p2051[x] or p2061[2x].
3. You must fill the unused slots of p8871[0...31] with zeros.
4. The sequence of the PZDs in the send telegram of this node are defined in parameter
p8871[0...31] by the entries in the required slots.
Receiving data
The sent telegrams of all nodes are simultaneously available at the SINAMICS Link. Each
telegram has a length of 32 PZD. Each telegram has a marker of the sender. You select
those PZD that you want to receive for the relevant node from all telegrams. You can
process a maximum of 32 PZD.
Note
If you have not deactivated the evaluation of bit 10 with p2037 = 2, the first word of the
receive data (PZD
1) must be a control word, where bit 10 = 1 is set.
In this example, Control Unit 2 receives selected data from the telegram of Control Unit 1.
Proceed as follows to receive data:
1. In parameter p8872[0…31] enter the address of the node for which you want to read one
or more PZDs (e.g. p8872[3] = 1 → from node 1, read in PZD 4, p8872[15] = 0 → do not
read in PZD 16).
2. After setting the parameters, using parameter r2050[0…31] or r2060[0…31] you can read
out the values.

Table of Contents

Other manuals for Siemens SINAMICS DCM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS DCM and is the answer not in the manual?

Siemens SINAMICS DCM Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS DCM
CategoryMedia Converter
LanguageEnglish

Related product manuals