1522A 67-TOC MEASUR. Fundamental
True RMS
Fundamental 67-TOC measurement of
1530 67 1.00 .. 20.00 I/Ip;
0.01 .. 999.00 TD
67
1531 MofPU Res T/Tp 0.05 .. 0.95 I/Ip;
0.01 .. 999.00 TD
Multiple of Pickup <-> T/Tp
1601 FCT 67N/67N-TOC OFF
ON
OFF 67N, 67N-TOC Ground
Time Overcurrent
1602 67N-2 PICKUP 1A 0.05 .. 35.00 A; 0.50 A 67N-2 Pickup
5A 0.25 .. 175.00 A; 2.50 A
1603 67N-2 DELAY 0.00 .. 60.00 sec; 0.10 sec 67N-2 Time Delay
1604 67N-1 PICKUP 1A 0.05 .. 35.00 A; 0.20 A 67N-1 Pickup
5A 0.25 .. 175.00 A; 1.00 A
1605 67N-1 DELAY 0.00 .. 60.00 sec; 0.50 sec 67N-1 Time Delay
1607 67N-TOC PICKUP 1A 0.05 .. 4.00 A 0.20 A 67N-TOC Pickup
5A 0.25 .. 20.00 A 1.00 A
1608 67N-TOC T-DIAL 0.05 .. 3.20 sec; 0.20 sec 67N-TOC Time Dial
1609 67N-TOC T-DIAL 0.50 .. 15.00 ; 5.00 67N-TOC Time Dial
1610 67N-TOC DropOut Instantaneous
Disk Emulation
Disk Emulation Drop-Out Characteristic
1611 67N-TOC IEC Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
Normal Inverse IEC Curve
1612 67N-TOC ANSI Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
Very Inverse ANSI Curve
1613A MANUAL CLOSE 67N-2 instant.
67N-1 instant.
67N-TOC instant
Inactive
67N-2 instant. Manual Close Mode
1614A 67N-2 active always
with 79 active
always 67N-2 active
1616 67N Direction Forward
Reverse
Forward Ground Direction
1617 67N POLARIZAT. with VN and IN
with V2 and I2
with VN and IN Ground Polarization
1618A 67N T DROP-OUT 0.00 .. 60.00 sec 0.00 sec 67N Drop-Out Time Delay
1619A ROTATION ANGLE -180 .. 180 ° -45 ° Rotation Angle of Refer-
ence Voltage
1620A 67N-2 MEASUREM. Fundamental
True RMS
Fundamental 67N-2 measurement of
Addr. Parameter C Setting Options Default Setting Comments
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens SIPROTEC 7SJ62

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SJ62 and is the answer not in the manual?

Siemens SIPROTEC 7SJ62 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SJ62
CategoryRelays
LanguageEnglish

Related product manuals