2.23.5.3 Settings
2.23.5.4 Information List
Addr. Parameter Setting Options Default Setting Comments
8311 MinMax cycRESET NO
YES
YES Automatic Cyclic Reset Function
8312 MiMa RESET TIME 0 .. 1439 min 0 min MinMax Reset Timer
8313 MiMa RESETCYCLE 1 .. 365 Days 7 Days MinMax Reset Cycle Period
8314 MinMaxRES.START 1 .. 365 Days 1 Days MinMax Start Reset Cycle in
No. Information Type of In-
formation
Comments
- ResMinMax IntSP_Ev Reset Minimum and Maximum counter
395 >I MinMax Reset SP >I MIN/MAX Buffer Reset
396 >I1 MiMaReset SP >I1 MIN/MAX Buffer Reset
397 >V MiMaReset SP >V MIN/MAX Buffer Reset
398 >VphphMiMaRes SP >Vphph MIN/MAX Buffer Reset
399 >V1 MiMa Reset SP >V1 MIN/MAX Buffer Reset
400 >P MiMa Reset SP >P MIN/MAX Buffer Reset
401 >S MiMa Reset SP >S MIN/MAX Buffer Reset
402 >Q MiMa Reset SP >Q MIN/MAX Buffer Reset
403 >Idmd MiMaReset SP >Idmd MIN/MAX Buffer Reset
404 >Pdmd MiMaReset SP >Pdmd MIN/MAX Buffer Reset
405 >Qdmd MiMaReset SP >Qdmd MIN/MAX Buffer Reset
406 >Sdmd MiMaReset SP >Sdmd MIN/MAX Buffer Reset
407 >Frq MiMa Reset SP >Frq. MIN/MAX Buffer Reset
408 >PF MiMaReset SP >Power Factor MIN/MAX Buffer Reset
412 > Θ MiMa Reset SP >Theta MIN/MAX Buffer Reset
837 IAdmdMin MVT I A Demand Minimum
838 IAdmdMax MVT I A Demand Maximum
839 IBdmdMin MVT I B Demand Minimum
840 IBdmdMax MVT I B Demand Maximum
841 ICdmdMin MVT I C Demand Minimum
842 ICdmdMax MVT I C Demand Maximum
843 I1dmdMin MVT I1 (positive sequence) Demand Minimum
844 I1dmdMax MVT I1 (positive sequence) Demand Maximum
845 PdMin= MVT Active Power Demand Minimum
846 PdMax= MVT Active Power Demand Maximum
847 QdMin= MVT Reactive Power Demand Minimum
848 QdMax= MVT Reactive Power Demand Maximum
849 SdMin= MVT Apparent Power Demand Minimum
850 SdMax= MVT Apparent Power Demand Maximum
851 Ia Min= MVT Ia Min
852 Ia Max= MVT Ia Max
853 Ib Min= MVT Ib Min
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens SIPROTEC 7SJ62

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SJ62 and is the answer not in the manual?

Siemens SIPROTEC 7SJ62 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SJ62
CategoryRelays
LanguageEnglish

Related product manuals