Functions
2.6 Voltage Protection 27, 59
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
150
2.6.6 Information List
5103 27-1 PICKUP 10 .. 120 V 75 V 27-1 Pickup
5106 27-1 DELAY 0.00 .. 100.00 sec; ∞ 1.50 sec 27-1 Time Delay
5110 27-2 PICKUP 10 .. 210 V 70 V 27-2 Pickup
5111 27-2 PICKUP 10 .. 120 V 70 V 27-2 Pickup
5112 27-2 DELAY 0.00 .. 100.00 sec; ∞ 0.50 sec 27-2 Time Delay
5113A 27-1 DOUT RATIO 1.01 .. 3.00 1.20 27-1 Dropout Ratio
5114A 27-2 DOUT RATIO 1.01 .. 3.00 1.20 27-2 Dropout Ratio
5120A CURRENT SUPERV. OFF
ON
ON Current Supervision
No. Information Type of In-
formation
Comments
234.2100 27, 59 blk IntSP 27, 59 blocked via operation
6503 >BLOCK 27 SP >BLOCK 27 undervoltage protection
6505 >27 I SUPRVSN SP >27-Switch current supervision ON
6506 >BLOCK 27-1 SP >BLOCK 27-1 Undervoltage protection
6508 >BLOCK 27-2 SP >BLOCK 27-2 Undervoltage protection
6513 >BLOCK 59 SP >BLOCK 59 overvoltage protection
6530 27 OFF OUT 27 Undervoltage protection switched OFF
6531 27 BLOCKED OUT 27 Undervoltage protection is BLOCKED
6532 27 ACTIVE OUT 27 Undervoltage protection is ACTIVE
6533 27-1 picked up OUT 27-1 Undervoltage picked up
6534 27-1 PU CS OUT 27-1 Undervoltage PICKUP w/curr. superv
6537 27-2 picked up OUT 27-2 Undervoltage picked up
6538 27-2 PU CS OUT 27-2 Undervoltage PICKUP w/curr. superv
6539 27-1 TRIP OUT 27-1 Undervoltage TRIP
6540 27-2 TRIP OUT 27-2 Undervoltage TRIP
6565 59 OFF OUT 59-Overvoltage protection switched OFF
6566 59 BLOCKED OUT 59-Overvoltage protection is BLOCKED
6567 59 ACTIVE OUT 59-Overvoltage protection is ACTIVE
6568 59-1 picked up OUT 59 picked up
6570 59-1 TRIP OUT 59 TRIP
6571 59-2 picked up OUT 59-2 Overvoltage V>> picked up
6573 59-2 TRIP OUT 59-2 Overvoltage V>> TRIP
Addr. Parameter Setting Options Default Setting Comments
www . ElectricalPartManuals . com