2.19.1.10 Information List
6141 F SYNCHRON 0.01 .. 0.04 Hz 0.01 Hz Frequency threshold ASYN <-->
SYN
6142 dV SYNC V2>V1 0.5 .. 50.0 V 5.0 V Maximum voltage difference
V2>V1
6143 dV SYNC V2<V1 0.5 .. 50.0 V 5.0 V Maximum voltage difference
V2<V1
6144 dα SYNC α2> α1 2 .. 80 ° 10 ° Maximum angle difference
alpha2>alpha1
6145 dα SYNC α2< α1 2 .. 80 ° 10 ° Maximum angle difference
alpha2<alpha1
6146 T SYNC-DELAY 0.00 .. 60.00 sec 0.00 sec Release delay at synchronous
conditions
6150 dV SYNCHK V2>V1 0.5 .. 50.0 V 5.0 V Maximum voltage difference
V2>V1
6151 dV SYNCHK V2<V1 0.5 .. 50.0 V 5.0 V Maximum voltage difference
V2<V1
6152 df SYNCHK f2>f1 0.01 .. 2.00 Hz 0.10 Hz Maximum frequency difference
f2>f1
6153 df SYNCHK f2<f1 0.01 .. 2.00 Hz 0.10 Hz Maximum frequency difference
f2<f1
6154 dα SYNCHK α2>α1 2 .. 80 ° 10 ° Maximum angle difference
alpha2>alpha1
6155 dα SYNCHK α2<α1 2 .. 80 ° 10 ° Maximum angle difference
alpha2<alpha1
No. Information Type of In-
formation
Comments
170.0001 >25-1 act SP >25-group 1 activate
170.0043 >25 Sync req. SP >25 Syncronization request
170.0049 25 CloseRelease OUT 25 Sync. Release of CLOSE Command
170.0050 25 Sync. Error OUT 25 Synchronization Error
170.0051 25-1 BLOCK OUT 25-group 1 is BLOCKED
170.2007 25 Measu. req. SP 25 Sync. Measuring request of Control
170.2008 >BLK 25-1 SP >BLOCK 25-group 1
170.2009 >25direct CO SP >25 Direct Command output
170.2011 >25 Start SP >25 Start of synchronization
170.2012 >25 Stop SP >25 Stop of synchronization
170.2013 >25 V1>V2< SP >25 Switch to V1> and V2<
170.2014 >25 V1<V2> SP >25 Switch to V1< and V2>
170.2015 >25 V1<V2< SP >25 Switch to V1< and V2<
170.2016 >25 synchr. SP >25 Switch to Sync
170.2022 25-1 meas. OUT 25-group 1: measurement in progress
170.2025 25 MonTimeExc OUT 25 Monitoring time exceeded
170.2026 25 Synchron OUT 25 Synchronization conditions okay
Addr. Parameter Setting Options Default Setting Comments
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens SIPROTEC 7SJ62

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SJ62 and is the answer not in the manual?

Siemens SIPROTEC 7SJ62 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SJ62
CategoryRelays
LanguageEnglish

Related product manuals