figure 8-18 Active Power Regulation
table 8-8 Description of active power regulation
Parameter
Description
Default
Range
Active Power Soft
Start after Fault
Switch for activating/deactivating the
function of active power soft start after
a fault occurs
On On/Off
Active Power Soft
Start Time after
Fault
The soft start time required for raising
active power from 0 to rated value
after a fault occurs
600s 1s ~ 1200s
Active Power Gra-
dient Control
Set whether to enable active power
gradient control
On On/Off
Active Power De-
cline Gradient
Decline gradient of inverter active
power per minute
39%/min
1%/min ~
6000%/min
Active Power Ris-
ing Gradient
Rising gradient of inverter active
power per minute
Active Power Set-
ting Persistence
Switch for activating/deactivating the
function of active power setting
persistence
Off On/Off
Active Power Limit
Switch for limiting active power
On On/Off
Active Power Limit
Ratio
The ratio of active power limit to rated
power in percentage
100.0% 0 ~ 100%
8.10.7 Reactive Power Regulation
Tap Settings→Power Regulation Parameters→Reactive Power Regulationto enter the
screen, as shown in the following figure.
User Manual 8 iSolarCloud App

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow SH10T and is the answer not in the manual?

Sungrow SH10T Specifications

General IconGeneral
BrandSungrow
ModelSH10T
CategoryInverter
LanguageEnglish

Related product manuals