Start-Up
Motor-Related Checks
Locate installation manual from the motor manufacturer for the specific motor installed. This
can be found by contacting the motor manufacturers representative. The motor
manufacturers recommendations take precedence for all matters related to the start-up and
routine maintenance of the motor.
Check the motor lubrication for moisture and rust.
Remove and clean grease plugs to inspect.
If moisture is present, consult an authorized repair shop for bearing inspection/replacement.
This may require removal and transport of motor.
If no moisture is present, refer to the motor manufacturers lubrication recommendations for
proper lubrication.
The motor manufacturer may recommend lubricating the motor as part of their routine start-
up instructions.
Check motor winding. An acceptable winding resistance reading is from 6 meg-ohms to infinity.
If reading is less than 5 mega-ohms, the winding should be dried out in an oven or by a blower.
Inspect the entire motor for rust and corrosion.
Bump-start the unit and confirm the fan wheel rotates properly, as indicated by the rotation
arrow located on the fan housing.
Note: For motor warranty needs, contact your local Trane sales office.
Unit Operation
WARNING
Rotating Components!
During installation, testing, servicing and troubleshooting of this product it may be necessary to
measure the speed of rotating components. Have a qualified or licensed service individual who
has been properly trained in handling exposed rotating components, perform these tasks.
Failure to follow all safety precautions when exposed to rotating components could result in
death or serious injury.
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary
to work with live electrical components. Have a qualified licensed electrician or other individual
who has been properly trained in handling live electrical components perform these tasks.
Failure to follow all electrical safety precautions when exposed to live electrical components
could result in death or serious injury.
Before complete start-up, bump-start the unit and confirm the fan wheel rotates properly, as
indicated by the rotation arrow located on the fan housing.
After initial startup:
Calculate the motor voltage imbalance, notifying the power company to correct unacceptable
imbalances.
Periodically check the fan belt tension.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane AM4A0A30S21SA Series and is the answer not in the manual?

Trane AM4A0A30S21SA Series Specifications

General IconGeneral
BrandTrane
ModelAM4A0A30S21SA Series
CategoryAir Handlers
LanguageEnglish

Related product manuals