28
Section 13. Electrical - Low Voltage
13.1 Low Voltage Maximum Wire Length
Table 11.1 defines the maximum total length of low
voltage wiring from the outdoor unit, to the indoor
unit, and to the thermostat.
Table 13.1
24 VOLTS
WIRE SIZE MAX. WIRE LENGTH
18 AWG 150 Ft.
16 AWG 225 Ft.
14 AWG 300 Ft.
13.2 Low Voltage Hook-up Instructions
STEP 1 - Route control wiring to unit. Remove the
external sheathing of the wiring approximately 5”.
STEP 2 - Remove Coil panel by turning the quarter
turn Phillips head door fasteners, rotating the door
away from the cabinet, and removing.
5”