10 Drive Start-Up
YASKAWA TOEPC71061752B GA500 Drive Installation & Primary Operation 79
Figure 10.2 View and Set the Necessary Parameters
Continue to change the parameters or press and hold to go back to the frequency reference
screen.
Automatic Parameter Settings Optimized for Specific Applications (Application
Presets)
Show the frequency reference screen.
Note:
Press and hold to return to the frequency reference screen from any screen.
Use this procedure to set an application preset.
The drive has application presets to set the necessary parameters for different applications to
their best values. Use to find parameters that were changed automatically by the
application preset function in A1-06.
Note:
Before you set A1-06, make sure that you set A1-03 = 2220, 3330 [Initialize Parameters = 2-Wire Initialization, 3-Wire
Initialization] to initialize parameters.
Figure 10.3 Automatic Parameter Settings
Press and hold to go back to the frequency reference screen.
Note:
You cannot directly set parameter A1-06. To set an application preset, first set A1-03 = 2220 to initialize parameters,
then set this parameter. If initializing all parameters will cause a problem, do not change the settings.
When the drive applies the A1-06 setting, it will also reset the parameters automatically registered to A2-17 to A2-32
[User Parameters 17 to 32] when A2-33 = 1 [User Parameter Auto Selection = Enabled: Auto Save Recent Parms].