256 Parameters
45.19 Comparison power Actual power that the motor absorbs when connected
direct-on-line and operating the application. The value is
used for reference when energy savings are calculated.
Note: The accuracy of the energy savings calculation is
directly dependent on the accuracy of this value. If nothing
is entered here, then the nominal motor power is used by
the calculation, but that may inflate the energy savings
reported as many motors do not absorb nameplate power.
0.00 kW
0.00…100000.00 kW Motor power. 1 = 1 kW
45.21 Energy calculations
reset
Resets the savings counter parameters 45.01…45.10. Done
Done Reset not requested (normal operation), or reset
complete.
0
Reset Reset the savings counter parameters. The value reverts
automatically to Done.
1
45.24 Hourly peak power
value
Value of the peak power during the last hour, that is, the
most recent 60 minutes after the drive has been powered
up.
The parameter is updated once every 10 minutes unless
the hourly peak is found in the most recent 10 minutes. In
that case, the values is shown immediately.
0.00 kW
-3000.00 … 3000.00
kW
Peak power value. 10 = 1 kW
45.25 Hourly peak power
time
Time of the peak power value during the last hour. 00:00:00
Time. N/A
45.26 Hourly total energy
(resettable)
Total energy consumption during the last hour, that is, the
most recent 60 minutes.
You can reset the value by setting it to zero.
0.00 kWh
-3000.00 … 3000.00
kWh
Total energy. 10 = 1 kWh
45.27 Daily peak power
value (resettable)
Value of the peak power since midnight of the present
day.
You can reset the value by setting it to zero.
0.00 kW
-3000.00 … 3000.00
kW
Peak power value. 10 = 1 kW
45.28 Daily peak power time Time of the peak power since midnight of the present day. 00:00:00
Time. N/A
45.29 Daily total energy
(resettable)
Total energy consumption since midnight of the present
day.
You can reset the value by setting it to zero.
0.00 kWh
-30000.00 …
30000.00 kWh
Total energy. 1 = 1 kWh
45.30 Last day total energy Total energy consumption during the previous day, that is,
between midnight of the previous day and midnight of the
present day
0.00 kWh
-30000.00 …
30000.00 kWh
Total energy. 1 = 1 kWh
No. Name/Value Description Default
FbEq 16
ACS180 FW.book Page 256 Tuesday, March 9, 2021 2:25 PM