360 Fieldbus control through the embedded fieldbus interface (EFB)
Control Word
Control Word for the ABB Drives profile
The table below shows the contents of the fieldbus Control Word for the ABB Drives
control profile. The embedded fieldbus interface converts this word to the form in
which it is used in the drive. The upper case boldface text refers to the states shown
in State transition diagram for the ABB Drives profile on page 365.
Bit Name Value STATE/Description
0OFF1_
CONTROL
1 Proceed to READY TO OPERATE.
0 Stop along currently active deceleration ramp. Proceed to
OFF1 ACTIVE; proceed to READY TO SWITCH ON
unless other interlocks (OFF2, OFF3) are active.
1OFF2_
CONTROL
1 Continue operation (OFF2 inactive).
0 Emergency OFF, coast to stop.
Proceed to OFF2 ACTIVE, proceed to SWITCH-ON
INHIBITED.
2OFF3_
CONTROL
1 Continue operation (OFF3 inactive).
0 Emergency stop, stop within time defined by drive
parameter. Proceed to OFF3 ACTIVE; proceed to
SWITCH-ON INHIBITED.
Warning: Ensure that the motor and driven machine can
be stopped using this stop mode.
3 INHIBIT_
OPERATION
1 Proceed to OPERATION ENABLED.
Note: Run enable signal must be active; see the drive
documentation. If the drive is set to receive the Run
enable signal from the fieldbus, this bit activates the
signal. See also parameter 06.18 Start inhibit status word
(page 120).
0 Inhibit operation. Proceed to OPERATION INHIBITED.
4 RAMP_OUT_
ZERO
1 Normal operation. Proceed to RAMP FUNCTION
GENERATOR: OUTPUT ENABLED.
0 Force Ramp Function Generator output to zero. Drive
ramps to stop (current and DC voltage limits in force).
5 RAMP_HOLD 1 Enable ramp function. Proceed to RAMP FUNCTION
GENERATOR: ACCELERATOR ENABLED.
0 Halt ramping (Ramp Function Generator output held).
6 RAMP_IN_
ZERO
1 Normal operation. Proceed to OPERATING.
Note: This bit is effective only if the fieldbus interface is
set as the source for this signal by drive parameters.
0 Force Ramp Function Generator input to zero.
7 RESET 0=>1 Fault reset if an active fault exists. Proceed to SWITCH-
ON INHIBITED.
Note: This bit is effective only if the fieldbus interface is
set as the source for this signal by drive parameters.
0 Continue normal operation.
ACS180 FW.book Page 360 Tuesday, March 9, 2021 2:25 PM

Table of Contents

Other manuals for ABB ACS180

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS180 and is the answer not in the manual?

ABB ACS180 Specifications

General IconGeneral
BrandABB
ModelACS180
CategoryDC Drives
LanguageEnglish

Related product manuals