294 Parameters
99.13 ID run requested Selects the type of the motor identification routine (ID run)
performed at the next start of the drive. During the ID run,
the drive will identify the characteristics of the motor for
optimum motor control.
If no ID run has been performed yet (or if default
parameter values have been restored using parameter
96.06 Parameter restore), this parameter is automatically
set to Standstill, signifying that an ID run must be
performed.
After the ID run, the drive stops and this parameter is
automatically set to None.
Notes:
To ensure that the ID run can work properly, the drive
limits in group 30 Limits (maximum speed and
minimum speed, and maximum torque and minimum
torque) must to be large enough (the range specified by
the limits must be wide enough. If eg. speed limits are
less than the motor nominal speed, the ID run cannot
be completed.
• For the Advanced ID run, the machinery must always
be de-coupled from the motor.
With a permanent magnet or synchronous reluctance
motor, a Normal, Reduced or Standstill ID run requires
that the motor shaft is NOT locked and the load torque
is less than 10%.
Once the ID run is activated, it can be canceled by
stopping the drive.
The ID run must be performed every time any of the
motor parameters (99.04, 99.0699.12) have been
changed.
With scalar control mode (99.04 Motor control mode =
Scalar), the ID run is not requested automatically.
However, an ID run can be performed for more
accurate torque estimation.
Ensure that the Safe torque off and emergency stop
circuits (if any) are closed during the ID run.
Mechanical brake (if present) is not opened by the logic
for the ID run.
This parameter cannot be changed while the drive is
running.
None
None No motor ID run is requested. This mode can be selected
only if the ID run (Normal/Reduced/Standstill/Advanced)
has already been performed once.
0
No. Name/Value Description Default
FbEq 16
ACS180 FW.book Page 294 Tuesday, March 9, 2021 2:25 PM

Table of Contents

Other manuals for ABB ACS180

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS180 and is the answer not in the manual?

ABB ACS180 Specifications

General IconGeneral
Product TypeDC Drive
Number of Phases1 or 3
IP RatingIP20
Communication InterfacesModbus RTU
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit
Operating Temperature-10°C to +50°C
Storage Temperature-40 to +70 °C
Relative Humidity5 to 95 % non-condensing
AltitudeUp to 1000 m