Page #340 background imageLoading...
Page #340 background image
340 Fault tracing
A983 External warning 3
(Editable message text)
Programmable warning:
31.05 External event 3
source
31.06 External event 3
type
Fault in external device 3. Check the external device.
Check setting of parameter 31.05
External event 3 source.
A984 External warning 4
(Editable message text)
Programmable warning:
31.07 External event 4
source
31.08 External event 4
type
Fault in external device 5. Check the external device.
Check setting of parameter 31.07
External event 4 source.
A985 External warning 5
(Editable message text)
Programmable warning:
31.09 External event 5
source
31.10 External event 5
type
Fault in external device 5. Check the external device.
Check setting of parameter 31.09
External event 5 source.
AF8C Process PID sleep
mode
The drive is entering sleep
mode.
Informative warning. See section Sleep
and boost functions for process PID
control, and parameters 40.4340.48.
AF90 Autotune The autotune routine has been
interrupted.
The code contains an auxiliary value that
specifies the reason for the abortion. For
details, see section Speed controller
autotune.
AFAA Autoreset A fault is about to be autoreset. Informative warning. See the settings in
parameter group 31 Fault functions.
AFE1 Emergency stop (off2) Drive has received an
emergency stop (mode
selection off2) command.
Check that it is safe to continue
operation. Then return emergency stop
push button to normal position. Restart
drive.
If the emergency stop was unintentional,
check the source selected by parameter
21.05 Emergency stop source.
AFE2 Emergency stop (off1
or off3)
Drive has received an
emergency stop (mode
selection off1 or off3)
command.
AFEA Enable start signal
missing
(Editable message text)
No enable start signal
received.
Check the setting of (and the source
selected by) parameter 20.19 Enable
start command.
AFE9 Start delay The start delay is active and
the drive will start the motor
after a predefined delay.
Informative warning. See parameter
21.22 Start delay.
AFEB Run enable missing No run enable signal is
received.
Check setting of parameter 20.12 Run
enable 1 source. Switch signal on (e.g. in
the fieldbus Control Word) or check
wiring of selected source.
AFED Enable to rotate Signal enable to rotate has not
been received within a fixed
time delay of 240s.
Switch enable to rotate signal on (eg. in
digital inputs).
Check the setting of (and source
selected by) parameter 20.22 Enable to
rotate.
AFF6 Identification run Motor ID run will occur at next
start.
Informative warning.
AFF7 Autophasing Autophasing will occur at next
start.
Informative warning.
Code
(hex)
Warning / Aux. code Cause What to do
ACS180 FW.book Page 340 Tuesday, March 9, 2021 2:25 PM

Table of Contents

Other manuals for ABB ACS180

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS180 and is the answer not in the manual?

ABB ACS180 Specifications

General IconGeneral
Product TypeDC Drive
Number of Phases1 or 3
IP RatingIP20
Communication InterfacesModbus RTU
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit
Operating Temperature-10°C to +50°C
Storage Temperature-40 to +70 °C
Relative Humidity5 to 95 % non-condensing
AltitudeUp to 1000 m

Related product manuals