Starting ACS580 drives for PROFINET
1. Power up the drive.
2. Enable the communication between the adapter module and the drive by setting parameter 50.01
FBA A Enable to Enable.
3. With parameter 50.02 FBA A comm loss func, select how the drive reacts to a fieldbus
communication break.
Note: This function monitors both communication between the fieldbus master and the adapter
module and communication between the adapter module and the drive.
4. With parameter 50.03 FBA A comm loss t out, define the time between communication break
detection and the selected action.
5. Select application-specific values for the rest of the parameters in group 50, starting from 50.04.
6. Set the FENA configuration parameters in group 51. At the minimum, set the 51.01 FBA A type as
Ethernet, 51.02 Protocol/Profile as PNIO ABB Pro(11), 51.04 IP configuration as Static, and required
IP address from parameter 51.05 to parameter 51.08 and 51.09 Subnet CDR as 24.
7. Define the process data transferred to and from the drive in FBA-01 configuration parameter groups
52 and 53.
Note: The adapter module sets the Status word and Control word automatically in parameters 52.01
and 53.01.
8. Validate the settings made in parameter groups 51, 54 and 55 by setting parameter 51.27 FBA PAR
REFRESH to REFRESH.
9. Save the valid parameter values to permanent memory by setting parameter 96.07 Parameter save
manually to Save.
10. Set the relevant drive control parameters to control the drive according to the application.

Table of Contents

Other manuals for ABB ACS880 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS880 Series and is the answer not in the manual?

ABB ACS880 Series Specifications

General IconGeneral
Cooling MethodAir-cooled, liquid-cooled
Enclosure classIP21, IP55
Mounting typeWall-mounted
Control methodDirect torque control (DTC)
Braking chopperIntegrated or external
CommunicationEthernet
Protection FeaturesOvercurrent, overvoltage, undervoltage, overload, short circuit, overtemperature, earth fault
Operating Temperature Range-15°C to +50°C
Storage Temperature Range-40°C to +70°C
Relative Humidity5 ... 95 % (non-condensing)
Safety featuresSafe torque off (STO)

Related product manuals