EasyManuals Logo

Carrier WeatherExpert 48N2 User Manual

Carrier WeatherExpert 48N2
248 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #234 background imageLoading...
Page #234 background image
234
APPENDIX G — OPTIONAL MOTORMASTER
®
V CONTROL
GENERAL
This appendix contains instructions for the start-up and ser-
vice of the optional Motormaster V (MMV) control on
48/50N 75-150 ton units.
The Motormaster V control is a motor speed control device
which adjusts condenser fan motor speed in response to an ana-
log signal from the unit ComfortLink controls. A properly ap-
plied Motormaster V control extends the operating range of air-
conditioning systems and permits operation at lower outdoor
ambient temperatures.
Location of Motormaster V device is in the unit power box.
See the power box component arrangement for details.
Configure Motormaster
®
V Control — The
Motormaster V control is configured for analog control mode.
The Motormaster V varies the condenser with an acceptable
head pressure. No additional programming is required. See
Table P.
Table P — Configuration Table
The following ComfortLink control configurations must be
set when using a Motormaster V device:
Configuration
COOL
M.M. = YES
Test Motormaster V Control — To test the control and
motor, see Service Test section.
START-UP
The Motormaster V electronic control will be powered up
as long as unit voltage is present. When the system calls for
cooling, the Motormaster relay (MMR) will be energized to
initiate the start-up sequence for the Motormaster V electronic
control. The LED (light-emitting diode) will display the speed
of the motor. The display range will be 8 to 60 Hz. The Motor-
master V electronic control will start the condenser fan when
the compressor engages. The ComfortLink controls will adjust
the fan speed via the Motormaster V electronic control to main-
tain approximately 320 psig. Above that pressure, the fan
should operate at full speed.
For all units, two Motormaster V devices are used, one for
each circuit. See Fig. M for typical Motormaster V wiring de-
tails. See Static Pressure Control section for details.
No field programming is required. If controller does not
function properly, the information provided in the Trouble-
shooting section can be used to program and troubleshoot the
drive.
NOMINAL
VOLTAGE
(V-Ph-Hz)
MODE
CONTROL INPUT
(Pin 5)
START
CONTACTS
230-3-60
460-3-60
575-3-60
1
Internal PI control,
0-5V feedback
TB 1,2
208-3-60
380-3-60
2 TB 13A,2
400-3-50 4 TB 13C,2
OFM6 (75)
OFM5 (90,105,120 STD-EFF)
OFM8 (90,105,120,130 HI-EFF)
OFM8 (130,150 STD-EFF)
Fig. M — Motormaster
®
V Wiring
LEGEND
CCB Control Circuit Breaker
MMF Motormaster V Fuses
MMR Motormaster V Relay
MMV Motormaster V Control
OFM Outdoor-Fan Motor
SCCR Short Circuit Current Rating
a48-8723

Table of Contents

Other manuals for Carrier WeatherExpert 48N2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier WeatherExpert 48N2 and is the answer not in the manual?

Carrier WeatherExpert 48N2 Specifications

General IconGeneral
BrandCarrier
ModelWeatherExpert 48N2
CategoryAir Conditioner
LanguageEnglish

Related product manuals