6-1
6. TROUBLESHOOTING
6.1 Refrigeration system and electrical system
If the unit does not work properly, refer to the following table to find causes of trouble and provide
appropriate measures.
Symptom Checkpoint RemedyCause
D. Condenser
fan and
compressor
run, but
evaporator fan
does not run.
Faulty electrical system
of evaporator fan
CTP running
Motor seizure
(disconnection)
Disconnected coil of
electromagnetic
contactor
External factor
E. Compressor runs,
but evaporator fan
and condenser
fan do not run.
Not malfunction
(defrost)
Controller display
E205 (Faulty 1 unit of EFM)
E803 (Faulty 2 units of EFM)
Motor coil resistance
Ensure that the electromagnetic contactor is turned ON
Voltage on secondary side of electromagnetic contactor
(three-phase)
Visual check for foreign matters caught in
and deformation
(including relevant parts such as controllers)
Check the lighting status of LED
(red) of DEF on control panel
A. Neither
evaporator
fan,
condenser
fan nor
compressor
runs.
Faulty power supply
Failure in running of
evaporator fan
Controller
B. Evaporator fan runs,
but condenser fan and
compressor do not run.
Not malfunction
(thermo-OFF
status)
C. Evaporator fan
and compressor
run,but
condenser fan
does not run.
Not malfunction (high
pressure control)
External factor
Check the power supply
Check the power supply plug
Check for disconnection of
cable
The unit is normal if the
condenser fan is
stopped while the HPT
is 1000 kPa or more
Replace faulty
equipment
Turn the switch ON
See the instructions for alarm code
of electronic controller in section 6.2
Replace the Fu
Replace faulty
equipment
Replace the
transformer
See the alarm code
when ALARM is issued
See section 6.2
Remove foreign matters
Replace the fan
motor
Replace the
electromagnetic
contactor
Remove foreign matters
Voltage on primary side of circuit
breaker
It should be within the voltage range
shown in page 1-1.
Ensure that the condenser fan is stopped
while high pressure is under control.
(Increase the high pressure
compulsorily, and make sure that the
evaporator fan stops when the HPT is
1000 kPa or more.)
Megger check on secondary side of
electromagnetic contactor
(Evaporator fan motor, condenser
fan motor, compressor)
Unit switch ON/OFF check
Alarm presence (F code)
Check for disconnection of Fu1 (fuse)
Check for malfunction in object
models shown in section 7.12
Check for disconnection on secondary
side of transformer (Tr)
Screwed crimp type terminal board:
Check of 24V at CN5
Connector type terminal board: Check
of 24V between lead wires 103 and 108
Display of controller
(ALARM display)
Check of operation of HPT (E101)
by controller display
Visual check for foreign matters caught in
and deformation
(including relevant parts such as controllers)
Secondary side of
power supply
transformer
Ⅰ Unit does not operate
06LXE10E-A(1-27)07.2.233:11PMページ6-1
https://daikin-p.ru

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin LXE10E-A and is the answer not in the manual?

Daikin LXE10E-A Specifications

General IconGeneral
BrandDaikin
ModelLXE10E-A
CategoryAir Conditioner
LanguageEnglish

Related product manuals