2-25
2.5.4 Dehumidification (Optional)
The unit have dehumidification control by a reheat coil, which is fitted under the evaporator coil.
To execute dehumidification, controller setting is required. (Refer to Page 3-12)
In dehumidification, the Reheat Solenoid Valve (RSV) opens to give high temperuture and high
pressurized refrigerant to reheat coil. The "DEHUMID" LED lamp will light up.
The following setting can be made:
1) Non humidification control
2) Humidification control (optional)
Dehumidification range: 60%RH–95%RH
02LXE10E-A(17-29)07.2.2015:39ページ2-25