Table 48: Cable Sizes for AFE or GC Module 525–690 V AC for Marine Applications (Marine cables according to IEC 60092-352) (continued)
Model code
Frame
(1)
I
N
[A] Mains cable Cu
[mm
2
]
Terminal max.
cable size
Number of
grounding
terminals/
bolt size
Max. number
of cables/
bolt size
iC7-60SLxx07-1700E00Fx 1740 12x(3x95) 150 Cu/Al 3/M8 18/M10
iC7-60SLxx07-1800E00Fx 1840 12x(3x95) 150 Cu/Al 3/M8 18/M10
iC7-60SLxx07-2000E00Fx 2050 12x(3x95) 150 Cu/Al 3/M8 18/M10
iC7-60SLxx07-2250E00Fx
3 x Ax12L
2300 12x(3x95) 150 Cu/Al 3/M8 18/M10
iC7-60SLxx07-2500E00Fx 2560 16x(3x95) 150 Cu/Al 4/M8 24/M10
iC7-60SLxx07-2650E00Fx 2710 20x(3x95) 150 Cu/Al 4/M8 24/M10
iC7-60SLxx07-2940E00Fx
4 x Ax12L
3002 20x(3x95) 150 Cu/Al 4/M8 24/M10
iC7-60SLxx07-3120E00Fx 3190 25x(3x95) 150 Cu/Al 5/M8 30/M10
iC7-60SLxx07-3600E00Fx
5 x Ax12L
3680 25x(3x95) 150 Cu/Al 5/M8 30/M10
iC7-60SLxx07-3900E00Fx 3990 30x(3x95) 150 Cu/Al 6/M8 36/M10
iC7-60SLxx07-4320E00Fx
6 x Ax12L
4410 30x(3x95) 150 Cu/Al 6/M8 36/M10
iC7-60SLxx07-4750E00Fx 4850 35x(3x95) 150 Cu/Al 7/M8 42/M10
iC7-60SLxx07-5040E00Fx
7 x Ax12L
5150 35x(3x95) 150 Cu/Al 7/M8 42/M10
iC7-60SLxx07-5400E00Fx 5520 40x(3x95) 150 Cu/Al 8/M8 48/M10
iC7-60SLxx07-5750E00Fx
8 x Ax12L
5870 40x(3x95) 150 Cu/Al 8/M8 48/M10
1) AM10L, AR10L, AM12L, or AR12L
10.4.6 Source Cable Sizes for DC/DC Converter Modules, 640–1100 V DC and 640–1200 V DC
Ambient air temperature maximum 60 °C (140 °F). Cable insulation is rated for minimum 90 °C (194 °F).
Use symmetrical cabling with modules connected in parallel. Each module must have the same number of cables with equal cross-
section.
Table 49: DC/DC Converter Module 640–1100VDC and 640–1200VDC Source Cable Sizes, IP00/Open Type.
Model code Frame Current (I
L
)
[A]
1-core cable
Cu [mm
2
]
3-core cable
Cu [mm
2
]
(1)
4-core cable
Cu [mm
2
]
(2)
Max.
Number of
terminals/
Bolt size
iC7-60SLDC07-300A 300 3x(1x95) 2x(3x70) 1x(4x70)
iC7-60SLDC07-360A 360 3x(1x95) 2x(3x70) 1x(4x70)
iC7-60SLDC07-420A 420 4x(1x95) 2x(3x95) 1x(4x95)
iC7-60SLDC07-480A 480 4x(1x95) 2x(3x95) 1x(4x95)
iC7-60SLDC07-570A
DR10L
570 4x(1x120) 2x(3x120) 1x(4x120)
4 / M10
172 | Danfoss Drives Oy © 2024.03 AJ475942178716en-000101 / 172K2848A
Design Guide | iC7 Series Liquid-cooled System Modules