EasyManuals Logo
Home>Danfoss>Media Converter>iC7 Series

Danfoss iC7 Series Design Guide

Danfoss iC7 Series
224 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #172 background imageLoading...
Page #172 background image
Table 48: Cable Sizes for AFE or GC Module 525–690 V AC for Marine Applications (Marine cables according to IEC 60092-352) (continued)
Model code
Frame
(1)
I
N
[A] Mains cable Cu
[mm
2
]
Terminal max.
cable size
Number of
grounding
terminals/
bolt size
Max. number
of cables/
bolt size
iC7-60SLxx07-1700E00Fx 1740 12x(3x95) 150 Cu/Al 3/M8 18/M10
iC7-60SLxx07-1800E00Fx 1840 12x(3x95) 150 Cu/Al 3/M8 18/M10
iC7-60SLxx07-2000E00Fx 2050 12x(3x95) 150 Cu/Al 3/M8 18/M10
iC7-60SLxx07-2250E00Fx
3 x Ax12L
2300 12x(3x95) 150 Cu/Al 3/M8 18/M10
iC7-60SLxx07-2500E00Fx 2560 16x(3x95) 150 Cu/Al 4/M8 24/M10
iC7-60SLxx07-2650E00Fx 2710 20x(3x95) 150 Cu/Al 4/M8 24/M10
iC7-60SLxx07-2940E00Fx
4 x Ax12L
3002 20x(3x95) 150 Cu/Al 4/M8 24/M10
iC7-60SLxx07-3120E00Fx 3190 25x(3x95) 150 Cu/Al 5/M8 30/M10
iC7-60SLxx07-3600E00Fx
5 x Ax12L
3680 25x(3x95) 150 Cu/Al 5/M8 30/M10
iC7-60SLxx07-3900E00Fx 3990 30x(3x95) 150 Cu/Al 6/M8 36/M10
iC7-60SLxx07-4320E00Fx
6 x Ax12L
4410 30x(3x95) 150 Cu/Al 6/M8 36/M10
iC7-60SLxx07-4750E00Fx 4850 35x(3x95) 150 Cu/Al 7/M8 42/M10
iC7-60SLxx07-5040E00Fx
7 x Ax12L
5150 35x(3x95) 150 Cu/Al 7/M8 42/M10
iC7-60SLxx07-5400E00Fx 5520 40x(3x95) 150 Cu/Al 8/M8 48/M10
iC7-60SLxx07-5750E00Fx
8 x Ax12L
5870 40x(3x95) 150 Cu/Al 8/M8 48/M10
1) AM10L, AR10L, AM12L, or AR12L
10.4.6 Source Cable Sizes for DC/DC Converter Modules, 640–1100 V DC and 640–1200 V DC
Ambient air temperature maximum 60 °C (140 °F). Cable insulation is rated for minimum 90 °C (194 °F).
Use symmetrical cabling with modules connected in parallel. Each module must have the same number of cables with equal cross-
section.
Table 49: DC/DC Converter Module 640–1100VDC and 640–1200VDC Source Cable Sizes, IP00/Open Type.
Model code Frame Current (I
L
)
[A]
1-core cable
Cu [mm
2
]
3-core cable
Cu [mm
2
]
(1)
4-core cable
Cu [mm
2
]
(2)
Max.
Number of
terminals/
Bolt size
iC7-60SLDC07-300A 300 3x(1x95) 2x(3x70) 1x(4x70)
iC7-60SLDC07-360A 360 3x(1x95) 2x(3x70) 1x(4x70)
iC7-60SLDC07-420A 420 4x(1x95) 2x(3x95) 1x(4x95)
iC7-60SLDC07-480A 480 4x(1x95) 2x(3x95) 1x(4x95)
iC7-60SLDC07-570A
DR10L
570 4x(1x120) 2x(3x120) 1x(4x120)
4 / M10
172 | Danfoss Drives Oy © 2024.03 AJ475942178716en-000101 / 172K2848A
Design Guide | iC7 Series Liquid-cooled System Modules

Table of Contents

Other manuals for Danfoss iC7 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss iC7 Series and is the answer not in the manual?

Danfoss iC7 Series Specifications

General IconGeneral
BrandDanfoss
ModeliC7 Series
CategoryMedia Converter
LanguageEnglish

Related product manuals