Design Guide | iC7 Series Liquid-cooled System Modules
Table 64: Current Ratings for Inverter Module, 380–500 VAC (465–800 VDC) (continued)
AC current Motor output power,
500 VAC
(2)(2)
Model code
(1)(1)
I
N
[A] I
L
[A] I
H
[A] I
peak
[A] P
L
[kW] P
H
[kW]
Frame Frame
with
option
+AExx
iC7-60SLINB5-2830E00F4 2889 2830 2122 4244 2600 1950 4 x IM12L 4 x IR12L
iC7-60SLINB5-3050E00F4 3114 3050 2287 4574 2800 2000 4 x IM12L 4 x IR12L
iC7-60SLINB5-3260E00F4 3328 3260 2445 4890 3000 2200 4 x IM12L 4 x IR12L
1) The hardware has improved transient withstand.
2) efficiency = 98.5%
10.6.8 Current Ratings for DC/DC Converter 640–1100 V DC-bus Voltage, IP00/Open Type
Table 65: Current Ratings for DC/DC Converter 640–1100VDC-bus Voltage, IP00/Open Type
DC bus
current
DC source current
(1)(1)
DC power, 1000...250VDC
source
Model code
I
N-DC
[A] I
N
[A] I
L
[A] I
H
[A] P
L-typ
[kW]
Frame Frame
with
option
+AE__
iC7-60SLDC07-300AE00F4 307 307 300 225 300...75 DM10L DR10L
iC7-60SLDC07-360AE00F4 368 368 360 270 360...90 DM10L DR10L
iC7-60SLDC07-420AE00F4 429 429 420 315 420...105 DM10L DR10L
iC7-60SLDC07-480AE00F4 490 490 480 360 480...120 DM10L DR10L
iC7-60SLDC07-570AE00F4 582 582 570 428 570...142 DM10L DR10L
iC7-60SLDC07-720AE00F4 735 735 720 540 720...180 DM12L DR12L
iC7-60SLDC07-840AE00F4 858 858 840 630 840...210 DM12L DR12L
iC7-60SLDC07-960AE00F4 980 980 960 720 960...240 DM12L DR12L
iC7-60SLDC07-1080E00F4 1103 1103 1080 810 1080...270 DM12L DR12L
iC7-60SLDC07-1200E00F4 1225 1225 1200 900 1200...300 DM12L DR12L
iC7-60SLDC07-1440E00F4 1470 1470 1440 1080 1440...360 2xDM12L 2xDR12L
iC7-60SLDC07-1680E00F4 1715 1715 1680 1260 1680...420 2xDM12L 2xDR12L
iC7-60SLDC07-1920E00F4 1960 1960 1920 1440 1920...480 2xDM12L 2xDR12L
iC7-60SLDC07-2160E00F4 2205 2205 2160 1620 2160...540 2xDM12L 2xDR12L
iC7-60SLDC07-2400E00F4 2450 2450 2400 1800 2400...600 2xDM12L 2xDR12L
iC7-60SLDC07-2880E00F4 2940 2940 2880 2160 2880...720 3xDM12L 3xDR12L
iC7-60SLDC07-3240E00F4 3308 3308 3240 2430 3240...810 3xDM12L 3xDR12L
iC7-60SLDC07-3600E00F4 3675 3675 3600 2700 3600...900 3xDM12L 3xDR12L
1) Sum of 3 phases.
Danfoss Drives Oy © 2024.03 AJ475942178716en-000101 / 172K2848A | 191