Design Guide | iC7 Series Liquid-cooled System Modules
Table 61: Current Ratings for Grid Converter Module, 525–690 VAC (640–1100 VDC) (continued)
AC current
(1)(1)
Power, 690 V AC
mains
Model code
I
N
[A] I
L
[A] I
H
[A] I
S1
[A] I
S2
[A] P
L
[kW] S
L
[kVA]
Frame Frame
with
option
+AEZ1
or
+AEZ3
(2)(2)
Input
L Filter
size
[A]
(3)(3)
iC7-60SLGC07-4750E00F4 4849 4750 3562 7125 6650 5564 5677 7 x
AM12L
7 x
AR12L
4 x 1640
iC7-60SLGC07-5040E00F4 5145 5040 3780 7560 7056 5903 6024 7 x
AM12L
7 x
AR12L
4 x 1640
iC7-60SLGC07-5400E00F4 5513 5400 4050 8100 7560 6325 6454 8 x
AM12L
8 x
AR12L
4 x 1640
iC7-60SLGC07-5750E00F4 5870 5750 4312 8625 8050 6735 6872 8 x
AM12L
8 x
AR12L
4 x 1640
1) I
S1
and I
S2
are intended for short-circuit current injection in grid forming operation. The rating is valid when the parameter Paralleling sync. Mode is disabled and the maximum
residual voltage of the fault is 30% of nominal at the grid converter terminals. Voltage measurement option OC7V0 is also required.
2) LC Filter +AEZ1, LCL Filter +AEZ3 (grid side L Filter separate module)
3) Part of LCL Filter, +AEZ3
10.6.5 Current Ratings for GC 380–500 V AC (465–800 V DC), IP00/Open Type
Table 62: Current Ratings for Grid Converter Module, 380–500 VAC (465–800 VDC)
AC current
(2)(2)
Power, 500 VAC
mains
Frame
Model code
(1)(1)
I
N
[A] I
L
[A] I
H
[A] I
S1
[A] I
S2
[A] P
L
[kW] S
L
[kVA]
Frame
with
option
+AEZ1
or
+AEZ3
(3)(3)
Input
L Filter
size
[A]
(4)(4)
iC7-60SLGCB5-261AE00F4 267 261 196 392 365 222 227 AM10L AR10L 400
iC7-60SLGCB5-325AE00F4 332 325 244 488 455 276 282 AM10L AR10L 400
iC7-60SLGCB5-380AE00F4 388 380 285 570 532 323 330 AM10L AR10L 400
iC7-60SLGCB5-425AE00F4 434 425 318 638 595 361 369 AM12L AR12L 1000
iC7-60SLGCB5-475AE00F4 485 475 356 713 665 404 412 AM12L AR12L 1000
iC7-60SLGCB5-530AE00F4 542 530 397 795 742 450 459 AM12L AR12L 1000
iC7-60SLGCB5-595AE00F4 608 595 446 893 833 505 516 AM12L AR12L 1000
iC7-60SLGCB5-670AE00F4 684 670 502 1005 938 569 581 AM12L AR12L 1000
iC7-60SLGCB5-760AE00F4 776 760 570 1140 1064 646 659 AM12L AR12L 1000
iC7-60SLGCB5-850AE00F4 868 850 637 1275 1190 722 737 2 x
AM12L
2 x
AR12L
1640
Danfoss Drives Oy © 2024.03 AJ475942178716en-000101 / 172K2848A | 187