Table 61: Current Ratings for Grid Converter Module, 525–690 VAC (640–1100 VDC) (continued)
AC current
(1)(1)
Power, 690 V AC
mains
Model code
I
N
[A] I
L
[A] I
H
[A] I
S1
[A] I
S2
[A] P
L
[kW] S
L
[kVA]
Frame Frame
with
option
+AEZ1
or
+AEZ3
(2)(2)
Input
L Filter
size
[A]
(3)(3)
iC7-60SLGC07-850AE00F4 868 850 637 1275 1190 996 1016 2 x
AM12L
2 x
AR12L
1640
iC7-60SLGC07-945AE00F4 965 945 708 1417.
5
1323 1107 1130 2 x
AM12L
2 x
AR12L
1640
iC7-60SLGC07-1040E00F4 1062 1040 780 1560 1456 1219 1243 2 x
AM12L
2 x
AR12L
1640
iC7-60SLGC07-1230E00F4 1256 1230 922 1845 1722 1441 1470 2 x
AM12L
2 x
AR12L
1640
iC7-60SLGC07-1325E00F4 1353 1325 993 1988 1855 1552 1584 2 x
AM12L
2 x
AR12L
1640
iC7-60SLGC07-1500E00F4 1532 1500 1125 2250 2100 1757 1793 2 x
AM12L
2 x
AR12L
1640
iC7-60SLGC07-1700E00F4 1736 1700 1275 2550 2380 1992 2032 3 x
AM12L
3 x
AR12L
2 x 1640
iC7-60SLGC07-1800E00F4 1838 1800 1350 2700 2520 2109 2152 3 x
AM12L
3 x
AR12L
2 x 1640
iC7-60SLGC07-2000E00F4 2042 2000 1500 3000 2800 2343 2391 3 x
AM12L
3 x
AR12L
2 x 1640
iC7-60SLGC07-2250E00F4 2297 2250 1687 3375 3150 2636 2690 3 x
AM12L
3 x
AR12L
2 x 1640
iC7-60SLGC07-2500E00F4 2552 2500 1875 3750 3500 2929 2988 4 x
AM12L
4 x
AR12L
2 x 1640
iC7-60SLGC07-2650E00F4 2706 2650 1987 3975 3710 3104 3168 4 x
AM12L
4 x
AR12L
2 x 1640
iC7-60SLGC07-2940E00F4 3002 2940 2205 4410 4116 3444 3514 4 x
AM12L
4 x
AR12L
2 x 1640
iC7-60SLGC07-3120E00F4 3185 3120 2340 4680 4368 3655 3729 5 x
AM12L
5 x
AR12L
3 x 1640
iC7-60SLGC07-3600E00F4 3675 3600 2700 5400 5040 4217 4303 5 x
AM12L
5 x
AR12L
3 x 1640
iC7-60SLGC07-3900E00F4 3982 3900 2925 5850 5460 4568 4661 6 x
AM12L
6 x
AR12L
3 x 1640
iC7-60SLGC07-4320E00F4 4410 4320 3240 6480 6048 5060 5163 6 x
AM12L
6 x
AR12L
3 x 1640
186 | Danfoss Drives Oy © 2024.03 AJ475942178716en-000101 / 172K2848A
Design Guide | iC7 Series Liquid-cooled System Modules