EasyManuals Logo
Home>Danfoss>Media Converter>iC7 Series

Danfoss iC7 Series Design Guide

Danfoss iC7 Series
224 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #91 background imageLoading...
Page #91 background image
Design Guide | iC7 Series Liquid-cooled System Modules
80
82
84
86
88
90
92
94
96
98
100
0
1
2
3 4 5 6 7 8 9 10
I/I
N
[%]
U
imb
[%]
e30bk460.10
Figure 94: Voltage Imbalance Derating
7.16.4 Derating of DC-bus Voltage
The drive can be used without derating up to 1025 V DC. For DC-bus voltages higher than 1025 V DC, current must be derated according
to the diagram.
86
88
90
92
94
96
98
100
640
680
720 760
800
840 880 920 960 1000 1040 1080
I/I
N
[%]
U
DC
[V]
e30bk461.10
Figure 95: DC-bus Voltage Derating
7.17 Modulator Types
The following are the available modulator types for AFE, GC, and INU modules. For more detailed descriptions and instructions on
modulator type selection, see the iC7 series application guides.
Modulator types for AFE and GC
Modulator type 4 – CMRPWM
l The default modulator type for AFE. This modulator can be used in the AFE to minimize motor voltage spikes. The modulator cannot
be used when independent paralleling is used (when Paralleling sync. Mode is enabled).
Danfoss Drives Oy © 2024.03 AJ475942178716en-000101 / 172K2848A | 91

Table of Contents

Other manuals for Danfoss iC7 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss iC7 Series and is the answer not in the manual?

Danfoss iC7 Series Specifications

General IconGeneral
BrandDanfoss
ModeliC7 Series
CategoryMedia Converter
LanguageEnglish

Related product manuals