Design Guide | iC7 Series Liquid-cooled System Modules
Table 74: Power Loss for INU Modules without Options, Modulator Type 2 (continued)
System
module, 2
kHz switching
frequency
System
module, 3
kHz switching
frequency
System
module, 4
kHz switching
frequency
System
module, 6
kHz switching
frequency
+AKF
X
(1)(1)
Model code Frame Rated
curre
nt
I
L(1/5)
[A]
Power
loss to
liquid
[kW]
Power
loss
to air
[kW]
Power
loss to
liquid
[kW]
Power
loss
to air
[kW]
Power
loss to
liquid
[kW]
Power
loss
to air
[kW]
Power
loss to
liquid
[kW]
Power
loss
to air
[kW]
Power
loss
to air
[kW]
iC7-60SLIN07-6100E
00F_
8xIM12L 6100 44.30 0.44 50.94 0.51 - - - - 0.67
iC7-60SLIN07-6400E
00F_
8xIM12L 6400 47.19 0.47 54.45 0.55 - - - - 0.77
1) DC fuses
10.7.10 Power Losses of INU Modules with +AEU1, Voltage Class B5, Motor Cable Maximum Length
150 m (492 ft)
l The specifications for the values in the table
¢ Inverter module
¢ 380–500 V AC (465–800 V DC)
¢ DC voltage 594 V DC
¢ Option +AEU1
¢ Switching frequency 2 kHz or 3 kHz
¢ Modulator type 2
¢ Motor cable length a maximum of 150 m (492 ft)
Table 75: Power Loss for INU Modules with Option +AEU1, Motor Cable Maximum Length 150 m (492 ft)
System module
and +AEU1,
2kHz switching
frequency
(1)(1)
System module
and +AEU1,
3kHz switching
frequency
(1)
+AKFX
(2)(2)
Model code Frame Rated
current
I
L(1/5)
[A]
Power
loss to
liquid
[kW]
Power
loss to
air [kW]
Power
loss to
liquid
[kW]
Power
loss to
air [kW]
Power
loss to
air [kW]
Standby
loss [kW]
iC7-60SLINB5-206AE00F_ IR10L 206 1.64 0.06 1.94 0.07 0.02 0.036
iC7-60SLINB5-245AE00F_ IR10L 245 1.97 0.07 2.31 0.08 0.02 0.036
iC7-60SLINB5-302AE00F_ IR10L 302 2.51 0.09 2.92 0.10 0.04 0.036
iC7-60SLINB5-385AE00F_ IR10L 385 3.55 0.14 4.12 0.15 0.04 0.036
iC7-60SLINB5-416AE00F_ IR10L 416 3.94 0.16 4.55 0.17 0.05 0.036
iC7-60SLINB5-525AE00F_ IR10L 525 4.05 0.13 4.82 0.15 0.04 0.072
Danfoss Drives Oy © 2024.03 AJ475942178716en-000101 / 172K2848A | 207