EasyManuals Logo
Home>Danfoss>Media Converter>iC7 Series

Danfoss iC7 Series Design Guide

Danfoss iC7 Series
224 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #182 background imageLoading...
Page #182 background image
Table 57: Source DC- Fuses for DC/DC Converter, Voltage Classes B5 and 07, IP00/Open Type (continued)
Model code
(1)(1)
Frame Rated
current
(I
L
) [A]
Number
of fuses
Fuse
size
Part number
(Mersen)
Fuse U
n
[V]
Fuse I
n
[A]
I
cp, mr
[A]
iC7-60SLDCxx-2880E00F4 2880 6 73 PC73UD13C800TF 1250 800 8900
iC7-60SLDCxx-3240E00F4 3240 6
iC7-60SLDCxx-3600E00F4
3 x DR12L
3600 6
73 PC73UD12C900TF 1200 900 10200
1) xx = B5 or 07
10.6 Current Ratings
10.6.1 List of Current Rating Information
The current rating tables show the ratings of the system modules at relevant voltage ratings. The current rating tables for the different
products can be found with these links.
l 10.6.2 Current Ratings for AFE 525–690 V AC (640–1100 V DC), IP00/Open Type
l 10.6.3 Current Ratings for AFE 380–500 V AC (465–800 V DC), IP00/Open Type
l 10.6.4 Current Ratings for GC 525–690 V AC (640–1100 V DC), IP00/Open Type
l 10.6.5 Current Ratings for GC 380–500 V AC (465–800 V DC), IP00/Open Type
l 10.6.6 Current Ratings for INU 525–690 V AC (640–1100 V DC), IP00/Open Type
l 10.6.7 Current Ratings for INU 380–500 V AC (465–800 V DC), IP00/Open Type
l 10.6.8 Current Ratings for DC/DC Converter 640–1100 V DC-bus Voltage, IP00/Open Type
l 10.6.9 Current Ratings for DC/DC Converter 465–800 V DC-bus Voltage, IP00/Open Type
Table 58: Abbreviations Used in the Rating Tables
Abbreviation Description
I
N
Nominal current. If the process does not require any overload-
ability or the process does not include any load variation or mar-
gin for overloadability, the dimensioning can be done according
to this current.
I
L
Nominal current with low overload (110%). Allows a +10% load
variation for 1 minute every 5 minutes.
I
H
Nominal current with high overload (150%). Allows a +50% load
variation for 1 minute every 5 minutes.
I
peak
Start current. Available for 3 s at start, then as long as the system
module temperature allows. Relevant for inverter modules.
I
S1
Short-term current injection available for 1 s. Applicable for the
grid converter control mode in grid forming in the event of short-
circuit current feed.
I
S2
Short-term current injection available for 0.5 s. Applicable for the
grid converter in the grid forming control mode in the event of
short-circuit current feed.
182 | Danfoss Drives Oy © 2024.03 AJ475942178716en-000101 / 172K2848A
Design Guide | iC7 Series Liquid-cooled System Modules

Table of Contents

Other manuals for Danfoss iC7 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss iC7 Series and is the answer not in the manual?

Danfoss iC7 Series Specifications

General IconGeneral
BrandDanfoss
ModeliC7 Series
CategoryMedia Converter
LanguageEnglish

Related product manuals