Use Combi M8 screws.
Use the tightening torque 20 Nm (177 in-lb).
Figure 66: Installing DC-terminal Busbars to the DC Terminals
3. Attach the DC fuse assemblies to the DC-terminal busbars and to the common DC busbars.
Use M10 screws and washers.
Use the tightening torque 35–40 Nm (310–354 in-lb).
The common DC busbars are not included in the delivery.
Figure 67: Installing DC Fuse Assemblies