14-52 Fan Control
Option: Function:
Select the minimum speed of the
main fan.
[0] * Auto Select [0] Auto to run the fan only
when the internal temperature of
the frequency converter is in the
range 35 °C (95 °F) to approxi-
mately 55 °C (131 °F). The fan runs
at low speed at 35 °C (95 °F) and
at full speed at approximately 55 °C
(131 °F).
[1] On 50%
[2] On 75%
[3] On 100%
[4] Auto (Low
temp env.)
14-53 Fan Monitor
Option: Function:
Select the frequency converter
action if a fan fault is detected.
[0] Disabled
[1] * Warning
[2] Trip
14-55 Output Filter
Option: Function:
NOTICE
This parameter cannot be
adjusted while the motor is
running.
NOTICE
Reset the frequency converter
after selecting [2] Sine-Wave
Filter Fixed.
CAUTION
OVERHEATING OF
FREQUENCY CONVERTER
When using sine-wave lters,
there is a risk of overheating
of the frequency converter,
which can result in personal
injury and equipment damage.
Always set
parameter 14-55 Output Filter
to [2] Sine-wave xed when
using a sine-wave lter.
Select the type of output lter
connected.
14-55 Output Filter
Option: Function:
[0] * No Filter This is the default setting and
should be used with dU/dt lters or
high-frequency common-mode (HF-
CM) lters.
[2] Sine Wave
Filter Fixed
This parameter sets a minimum
allowed limit to the switching
frequency and ensures that the
lter is operated within the safe
range of switching frequencies.
Operation is possible with all
control principles. For ux control
principle, program
parameter 14-56 Capacitance Output
Filter and
parameter 14-57 Inductance Output
Filter (these parameters have no
eect in VVC
+
and U/f ). The
modulation pattern is set to SFAVM,
which gives the lowest acoustic
noise in the lter.
14-59 Actual Number of Inverter Units
This parameter is only relevant for high-power frequency
converters.
Range: Function:
Size
related*
[ 1 - 1 ] Sets the actual number of
operating inverter units.
Parameter Descriptions Programming Guide
M0010001 Danfoss A/S © 10/2019 All rights reserved. 153
3 3

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals