Chapter 12 Description of Parameter SettingsC2000
12.1-14-2
When the setting for Pr. 14-18 or Pr. 14-19 are 0 or 1, the voltage input to AVI and ACI terminal
is 0–10 V or 4–20 mA. At this moment, Pr. 14-10 and Pr. 14-11 are invalid.
Setting 1 or 2: Displays the warning code “ANL” on the keypad. It continues blinking until the
lost ACI signal is recovered.
When the motor drive stops, the warning condition does not continue to exist, so the warning
disappears.
Extension Card Output Terminal Selection (AO10)
Extension Card Output Terminal Selection (AO11)
Default: 0
Settings 0–23
Refer to the function chart below for details setting.
Function Chart
Settings Functions Descriptions
0
Output frequency (Hz) Maximum frequency Pr.01-00 is processed as 100%.
1 Frequency command (Hz) Maximum frequency Pr.01-00 is processed as 100%.
2 Motor speed (Hz) Maximum frequency Pr.01-00 is processed as 100%.
3 Output current (rms) (2.5 ᵡ rated current) is processed as 100%
4 Output voltage (2 ᵡ rated voltage) is processed as 100%
5 DC BUS voltage 450V (900V)=100%
6 Power factor -1.000–1.000=100%
7 Power (2 ᵡ rated power) is processed as 100%
8 Torque Full load torque = 100%
9 AVI 0–10 V = 0–100%
10 ACI 4–20 mA = 0–100%
11 AUI -10–10V = 0–100%
12 Iq current command (2.5 ᵡ rated current) is processed as 100%
13 Iq feedback value (2.5 ᵡ rated current) is processed as 100%
14 Id current command (2.5 ᵡ rated current) is processed as 100%
15 Id feedback value (2.5 ᵡ rated current) is processed as 100%
18 Torque command Rated torque of motor = 100%
19 PG2 frequency command Maximum frequency Pr.01-00 is processed as 100%.
20 CANopen analog output For CANopen communication analog output
21 RS-485 analog output For RS-485 (InnerCOM / MODBUS) analog output
22
Communication card
analog output
For communication analog output (CMC-MOD01, CMC-EIP01,
CMC-PN01, CMC-DN01)
23 Constant voltage output
Pr. 03-32 controls the voltage output level.
0–100% of Pr. 03-32 corresponds to 0–10V of AFM.
25
CANopen and RS-485
analog output
For CANopen and InnerCOM control output

Table of Contents

Other manuals for Delta C2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Series and is the answer not in the manual?

Delta C2000 Series Specifications

General IconGeneral
BrandDelta
ModelC2000 Series
CategoryDC Drives
LanguageEnglish

Related product manuals