CHAPTER 5: SETTINGS INPUTS/OUTPUTS
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL 5-309
5
5.9.5.2 Graphical front panel
SETTINGS  INPUTS/OUTPUTS  RESETTING
Some events can be programmed to latch the front panel LED event indicators, target messages, and/or graphical front
panel annunciator windows. Once set, the latching mechanism holds the latched indicators, messages, or windows in the
set state after the initiating condition has cleared until a
RESET command is received to return these latches (not including
FlexLogic latches) to the reset state where the initiating condition has cleared. The
RESET command can be sent from the
front panel RESET button, a remote device via a communications channel, or any selected operand. The Modbus execute
function 05h with operation code 1 command is also available to perform the same function as the front panel RESET key.
RESET OPERAND — The three sources of RESET commands each activates the RESET OP FlexLogic operand. Each individual
source of a
RESET command also activates its individual operand RESET OP (PUSHBUTTON), RESET OP (COMMS), or RESET OP (OPERAND) to
identify the source of the command. Each of these three operands generates an event in the event record when activated.
The
RESET OPERAND setting here selects the operand that activates the RESET OP (OPERAND) operand.
RESET ANNUNCIATOR — Used to select a FlexLogic operand that when activated acknowledges/resets all annunciator
windows on the graphical front panel. The other methods to acknowledge/reset annunciator windows include:
On the displayed page, press the RESET pushbutton with none of the annunciator windows selected to acknowledge/
reset all annunciator windows on that page
To acknowledge/reset a specific annunciator window, use the Up, Down, Left and Right pushbuttons to select the
window, and press the RESET or ENTER pushbutton
All annunciator windows can be reset remotely by programming a Virtual Input (for example Virtual Input 1) as the
input to the
RESET ANNUNCIATOR setting. Then the Modbus execute function 05h with operation code 1000h command
(or function 10h with address 400h) is used to set the state of Virtual Input 1.
For the
RESET ANNUNCIATOR setting, the RESET ANCTR OP FlexLogic operand is activated by the two sources of RESET
command, operand source and manual source. Each individual source of a
RESET ANNUNCIATOR command also activates
its individual operand RESET OP (OPRD) or RESET ANCTR OP (MNUL) to identify the source of the command. Each of these two
operands generates an event in the event record when activated. The setting here selects the operand that activates the
RESET ANCTR OP (OPRD) operand. The RESET pushbutton on the front panel or the reset command from the software
activates the RESET ANCTR OP (MNUL) operand.
5.9.6 Direct inputs and outputs
5.9.6.1 Direct inputs
SETTINGS  INPUTS/OUTPUTS  DIRECT INPUTS DIRECT INPUT 1(32)
These settings specify how the direct input information is processed.
DIRECT INPUT 1 NAME — This setting allows the user to assign a descriptive name to the direct input.
RESETTING
RESET OPERAND:
Off
Range: FlexLogic operand
RESET ANNUNCIATOR:
Off
Range: FlexLogic operand
DIRECT INPUT 1
DIRECT INPUT 1
NAME: Dir Ip 1
Range: up to 12 alphanumeric characters
DIRECT INPUT 1
DEVICE ID: 0
Range: 0 to 16
DIRECT INPUT 1
BIT NUMBER: 0
Range: 0 to 32
DIRECT INPUT 1
DEFAULT: Off
Range: On, Off, Latest/On, Latest/Off
DIRECT INPUT 1
EVENTS: Disabled
Range: Enabled, Disabled